Skip to content
TradeCert Prep
Free lesson · 2026 refrigerant update

A2L and A3 refrigerant safety

4 min read · Lesson 1 of 3 in 2026 refrigerant update

The 2026 test bank adds general knowledge of mildly flammable and flammable refrigerants. This lesson covers the safety classes and what they mean on the job.

Key numbers

R-32 GWP
675
Source
R-454B GWP
470
Source
R-410A GWP
2,090
Source
A2L
Lower toxicity, lower flammability
Source

Safety classes

A2L means lower toxicity and lower flammability under ASHRAE Standard 34. R-454B is A2L: it is harder to ignite and burns more slowly than an A3 refrigerant, but it can burn, so follow the equipment and refrigerant safety instructions.

Source: EPA — Refrigerant Safety (ASHRAE Standard 34 classes).

Equipment and retrofits

R-32 and R-454B have EPA SNAP use conditions for specified new equipment, including design, labeling and service markings. EPA's SNAP listing allows R-454B for specified new equipment designed and identified for it; it is not a retrofit refrigerant for an existing R-410A system.

Source: EPA SNAP — Residential and light commercial AC and heat pumps.

Cylinders

AHRI Guideline N recommends light green-gray (RAL 7044) containers for all refrigerants, with a red band on the shoulder or top for flammable refrigerants. Read the cylinder label; do not identify refrigerant by color alone.

Source: AHRI Guideline N-2017 — Refrigerant container colors.

R-32 compared with R-454B

Neither is universally better. Both are A2L; R-32 is a single-component refrigerant with GWP 675 and no glide, while R-454B is a blend with GWP 470 and a small glide. The equipment manufacturer chooses the refrigerant for the system.

The EPA SNAP residential AC table lists GWP values of 2,090 for R-410A, 675 for R-32, 470 for R-454B, and 3 for R-290.

Source: EPA SNAP — Residential and light commercial AC and heat pumps.

Venting

R-32 and R-454B are non-exempt substitutes under the Section 608 venting rules: they may not be knowingly vented during service.

Source: 40 CFR 82.154 — Prohibitions.

Scenario

A technician recovering R-454B from a residential heat pump asks whether a small release during service is allowed. It is not: R-454B is a non-exempt substitute under Section 608, so it must be recovered, not vented.

Source: 40 CFR 82.154 — Prohibitions.

Check what you remember

1. In the ASHRAE Standard 34 safety class "A2L," what does the letter A mean?

Choices
Check answer

Correct answer: D. Lower toxicity

ASHRAE 34 uses a letter for toxicity (A = lower toxicity, B = higher toxicity) and a number for flammability. A2L refrigerants are lower-toxicity refrigerants.

Source: EPA – Refrigerant Safety (ASHRAE Standard 34 classes)

2. In the safety class "A2L," what does "2L" indicate?

Choices
Check answer

Correct answer: A. Lower flammability (mildly flammable)

The number is the flammability class: 1 = no flame propagation, 2L = lower flammability, 2 = flammable, 3 = higher flammability. 2L refrigerants burn slowly and are hard to ignite, but they can burn.

Source: EPA – Refrigerant Safety (ASHRAE Standard 34 classes)

3. What is the ASHRAE 34 safety classification of R-454B?

Choices
Check answer

Correct answer: A. A2L

R-454B (a blend of R-32 and R-1234yf) is listed by EPA SNAP as an A2L refrigerant: lower toxicity, lower flammability.

Source: EPA SNAP – Residential & light commercial AC and heat pumps

4. Which of these refrigerants is classified A1 (no flame propagation), not A2L?

Choices
Check answer

Correct answer: C. R-410A

R-410A is A1. R-32, R-454B and R-1234yf are all A2L (mildly flammable).

Source: EPA SNAP – Residential & light commercial AC and heat pumps

Keep going

2 more lessons in 2026 refrigerant update

All lessons and study tools are free with a signed-in account, so your progress stays saved.

Sign in for free access → Take a free practice test