The 2026 test bank adds general knowledge of mildly flammable and flammable refrigerants. This lesson covers the safety classes and what they mean on the job.
Key numbers
Safety classes
A2L means lower toxicity and lower flammability under ASHRAE Standard 34. R-454B is A2L: it is harder to ignite and burns more slowly than an A3 refrigerant, but it can burn, so follow the equipment and refrigerant safety instructions.
Source: EPA — Refrigerant Safety (ASHRAE Standard 34 classes).
Equipment and retrofits
R-32 and R-454B have EPA SNAP use conditions for specified new equipment, including design, labeling and service markings. EPA's SNAP listing allows R-454B for specified new equipment designed and identified for it; it is not a retrofit refrigerant for an existing R-410A system.
Source: EPA SNAP — Residential and light commercial AC and heat pumps.
Cylinders
AHRI Guideline N recommends light green-gray (RAL 7044) containers for all refrigerants, with a red band on the shoulder or top for flammable refrigerants. Read the cylinder label; do not identify refrigerant by color alone.
Source: AHRI Guideline N-2017 — Refrigerant container colors.
R-32 compared with R-454B
Neither is universally better. Both are A2L; R-32 is a single-component refrigerant with GWP 675 and no glide, while R-454B is a blend with GWP 470 and a small glide. The equipment manufacturer chooses the refrigerant for the system.
The EPA SNAP residential AC table lists GWP values of 2,090 for R-410A, 675 for R-32, 470 for R-454B, and 3 for R-290.
Source: EPA SNAP — Residential and light commercial AC and heat pumps.
Venting
R-32 and R-454B are non-exempt substitutes under the Section 608 venting rules: they may not be knowingly vented during service.
Source: 40 CFR 82.154 — Prohibitions.
Scenario
A technician recovering R-454B from a residential heat pump asks whether a small release during service is allowed. It is not: R-454B is a non-exempt substitute under Section 608, so it must be recovered, not vented.
Source: 40 CFR 82.154 — Prohibitions.