Refrigerant Recovery: Methods, Equipment and Cylinders

Quick answer: Refrigerant recovery means removing refrigerant from a system into an external recovery cylinder, without venting it, before opening or disposing of the system. Techs use a certified recovery machine (self-contained) or, on small appliances only, system-dependent methods. Recover liquid first to save time, never fill a recovery cylinder past 80%, and never vent refrigerant: it's illegal.

By the TradeCert Prep editorial team · Last reviewed: November 26, 2026 · How we research and check our content

Recover, recycle, reclaim

  • Recover: remove refrigerant from a system and store it in an external container, without testing or processing it.
  • Recycle: clean refrigerant for reuse by separating oil and passing it through filter-driers, usually on site.
  • Reclaim: reprocess refrigerant to the purity standard (AHRI 700) and verify it by analysis, at a reclaimer.

All three are EPA 608 Core topics (EPA test topics). Avoid mixing refrigerants: mixed refrigerant can be very hard or impossible to reclaim.

Recovery equipment: self-contained vs system-dependent

Types of recovery equipment
TypeHow it worksWhere it's allowed
Self-contained (active) recovery machineHas its own compressor; pumps refrigerant into a recovery cylinderAny appliance; required on systems with more than 15 lb
System-dependent (passive)Uses the appliance's compressor or pressureOnly appliances with 15 lb or less, such as small appliances

Recovery equipment must be certified by an EPA-approved third party (EPA test topics).

How to recover refrigerant faster

  • Recover liquid first, then vapor: liquid moves far more refrigerant per minute.
  • Push-pull uses vapor from the recovery cylinder to push liquid out of large systems.
  • Shorter, larger-diameter hoses and a warm ambient speed recovery; so does chilling the recovery cylinder or warming the appliance (never with an open flame).
  • Wait after reaching the required vacuum and watch for a pressure rise, which means liquid is still in the system.

Source: EPA test topics (Core and Type II recovery techniques).

How far you have to recover

Larger appliances must be evacuated to the levels in 40 CFR 82.156 Table 1 before opening or disposal; see evacuation and dehydration for the full table.

Small appliances (Type I)

  • Recovery equipment made before Nov. 15, 1993: recover 80% of the refrigerant. Equipment made on or after Nov. 15, 1993: recover 90% when the appliance compressor works, or 80% when it does not. Or evacuate the appliance to 4 in Hg vacuum.
  • System-dependent recovery equipment may not be used on appliances with a full charge of more than 15 lb unless it is permanently attached as a pump-out unit.

Recovery cylinders: color, fill limit and shipping

  • Gray body, yellow top. Reusable recovery cylinders must be DOT-approved and use this color code.
  • Never fill past 80% of capacity: liquid expands with heat and an overfilled cylinder can rupture from hydrostatic pressure.
  • Never use a disposable cylinder for recovery, and never refill one.
  • Label for shipping: cylinders of used refrigerant need the refrigerant identification and DOT classification labels.

Source: EPA test topics (Core safety and shipping).

On the EPA 608 exam

The three Rs, recovery equipment and cylinder rules are all Core topics.

Test yourself: 6 Core questions on recovery

The three Rs: recover, recycle, reclaimQuestion 1 of 6

Recovered refrigerant that is too contaminated or mixed to be reclaimed should be:

Answer choices for question 1

Keyboard: A–D to choose · Enter to check

The three Rs: recover, recycle, reclaimQuestion 2 of 6

Which of the 'three Rs' requires chemical analysis to verify purity?

Answer choices for question 2

Keyboard: A–D to choose · Enter to check

The three Rs: recover, recycle, reclaimQuestion 3 of 6

To 'recycle' refrigerant means to:

Answer choices for question 3

Keyboard: A–D to choose · Enter to check

The three Rs: recover, recycle, reclaimQuestion 4 of 6

Which of the following best describes the order of processing from least to most thorough?

Answer choices for question 4

Keyboard: A–D to choose · Enter to check

The three Rs: recover, recycle, reclaimQuestion 5 of 6

A technician removes refrigerant from a customer's unit, cleans it through a filter-drier on site and returns it to the same unit. This is:

Answer choices for question 5

Keyboard: A–D to choose · Enter to check

The three Rs: recover, recycle, reclaimQuestion 6 of 6

To 'recover' refrigerant means to:

Answer choices for question 6

Keyboard: A–D to choose · Enter to check

Recovery rules are on every EPA 608 test

Core is required for every certification. Check your recovery knowledge with a free timed section.

Take the free Core practice test

Frequently asked questions

What is a passive recovery device?

A system-dependent (passive) recovery method uses the appliance's own compressor or pressure, rather than a recovery machine, to move refrigerant into a container. EPA allows it only on appliances with 15 lb or less of refrigerant, such as small appliances.

Can I recover refrigerant without a recovery machine?

Only on small appliances, using system-dependent methods (for example running the appliance's compressor, or heating and striking an inoperative compressor). Larger systems need certified self-contained recovery equipment.

Why is it illegal to release refrigerant into the air?

The Clean Air Act prohibits knowingly venting ozone-depleting refrigerants and their substitutes during service, maintenance, repair or disposal, because they deplete ozone or contribute to climate change.

Does an AC vacuum pump remove refrigerant?

No. A vacuum pump is for evacuation after the refrigerant has been recovered. Running one on a charged system would vent refrigerant, which is illegal.

Sources