A2L Refrigerants Explained: R-32, R-454B, R-1234yf and Safe Handling

Quick answer: A2L refrigerants are lower-toxicity (A), lower-flammability (2L) refrigerants under ASHRAE Standard 34. R-32 and R-454B are replacing R-410A in new residential AC and heat pumps because of their lower GWP. They can burn, but are hard to ignite and burn slowly. EPA allows them only in new equipment designed for them, with red-marked service ports, and venting them is illegal under Section 608.

Last reviewed: November 24, 2026

ASHRAE 34 safety classes

ASHRAE refrigerant safety class meaning and examples
Part of classMeaningExamples
Toxicity letter ALower toxicityR-410A, R-32, R-454B
Toxicity letter BHigher toxicityB1: R-123, R-514A; B2L: ammonia (R-717)
Class 1No flame propagationA1: R-410A, R-134a, R-22
Class 2LLower flammability; maximum burning velocity of 10 cm/sA2L: R-32, R-454B, R-1234yf; B2L: ammonia (R-717)
Class 2FlammableSee the applicable refrigerant safety data and equipment labeling
Class 3Higher flammabilityA3: R-290 (propane), R-600a (isobutane)

ASHRAE’s class combines a toxicity letter and a flammability number. A2L refrigerants are lower-toxicity and lower-flammability, not nonflammable.

Compare common refrigerants and P-T values

These pressure values come from the site’s P-T chart data at 40°F, 75°F, and 100°F. For blends, each cell shows liquid/bubble pressure followed by vapor/dew pressure. Single-component refrigerants use one pressure value.

Safety class, ODP, GWP, and P-T chart pressures for six refrigerants
RefrigerantASHRAE classODPGWP40°F pressure (psig)75°F pressure (psig)100°F pressure (psig)
R-410AA102,090118.8 / 118.4 psig218.7 / 217.9 psig318.5 / 317.6 psig
R-32A2L0675121.0 psig223.2 psig325.7 psig
R-454BA2L0470113.2 / 107.5 psig208.4 / 199.5 psig303.3 / 291.9 psig
R-1234yfA2L0See EPA SNAP38.4 psig81.3 psig124.9 psig
R-290A30363.9 psig119.5 psig173.9 psig
R-600aA30See EPA SNAP11.9 psig34.5 psig57.9 psig

EPA’s SNAP residential AC table lists GWP values of R-410A 2,090, R-32 675, R-454B 470, and R-290 3. For R-1234yf and R-600a, see EPA SNAP. These P-T values are provided for study and reference; confirm with the manufacturer for field work.

EPA SNAP use conditions for R-32 and R-454B

EPA’s May 6, 2021 SNAP rule lists these refrigerants for specified new residential and light commercial AC and heat-pump equipment, subject to use conditions.

  • New equipment only: equipment must be designed and identified for that refrigerant; the listing does not authorize retrofitting an R-410A system.
  • Safety standard: meet UL 60335-2-40, 3rd edition, including charge limits based on room size and the listed safeguards.
  • Warnings: equipment must carry the required warning labels.
  • Red service markings: use red PMS #185 or RAL 3020 at service ports and other places the refrigerant circuit can be opened. Markings extend at least 1 inch (25 mm) in both directions and must be replaced if removed.

A2L cylinders and recovery cylinders

  • AHRI Guideline N recommends light green-gray (RAL 7044) for refrigerant containers generally and a red band on the shoulder or top for flammable refrigerants.
  • Most A2L disposable cylinders use a left-hand-thread outlet and a resettable pressure relief valve instead of a rupture disc.
  • AHRI Guideline K specifies left-hand threads for recovery cylinders holding flammable refrigerants.
  • Always identify refrigerant by its label, not color alone.

Venting and recovery

R-32 and R-454B are non-exempt substitutes: knowingly venting them during service is prohibited, and recovery equipment must be certified for the refrigerant and appliance. Section 608 exemptions apply only to named substitutes in specific end uses.

For example, R-600a is exempt in household refrigerators and freezers, and R-290 is exempt in listed end uses such as self-contained room ACs and stand-alone retail food units. Those exemptions do not authorize R-290 in split-system central AC.

A2L/A3 field practices

  • Ventilate the work area and keep ignition sources away.
  • Recover refrigerant before brazing, then purge with dry nitrogen. Never use oxygen to pressure-test or purge a refrigeration system.
  • Charge zeotropic blends such as R-454B as liquid to avoid changing blend composition.
  • For blend measurements, use dew pressure for superheat and bubble pressure for subcooling.

Related tools: superheat calculator and subcooling calculator.

Free 10-question A2L and A3 quiz

A2L, A3 & low-GWP refrigerantsQuestion 1 of 10

In the ASHRAE Standard 34 safety class "A2L," what does the letter A mean?

Answer choices for question 1

Keyboard: A–D to choose · Enter to check

A2L, A3 & low-GWP refrigerantsQuestion 2 of 10

Propane (R-290) and isobutane (R-600a) are in which ASHRAE safety class?

Answer choices for question 2

Keyboard: A–D to choose · Enter to check

A2L, A3 & low-GWP refrigerantsQuestion 3 of 10

Under AHRI Guideline N, what marks a container holding a flammable refrigerant?

Answer choices for question 3

Keyboard: A–D to choose · Enter to check

A2L, A3 & low-GWP refrigerantsQuestion 4 of 10

Under Section 608, may a technician knowingly vent R-454B from a residential heat pump during service?

Answer choices for question 4

Keyboard: A–D to choose · Enter to check

A2L, A3 & low-GWP refrigerantsQuestion 5 of 10

What does LFL (lower flammability limit) describe?

Answer choices for question 5

Keyboard: A–D to choose · Enter to check

A2L, A3 & low-GWP refrigerantsQuestion 6 of 10

Under the SNAP use conditions, how far must the red A2L marking extend from each service port?

Answer choices for question 6

Keyboard: A–D to choose · Enter to check

A2L, A3 & low-GWP refrigerantsQuestion 7 of 10

What color marks the service ports, pipes and hoses of new residential AC equipment using an A2L refrigerant?

Answer choices for question 7

Keyboard: A–D to choose · Enter to check

A2L, A3 & low-GWP refrigerantsQuestion 8 of 10

R-32 is a single-component refrigerant. What does that mean for its P-T chart?

Answer choices for question 8

Keyboard: A–D to choose · Enter to check

A2L, A3 & low-GWP refrigerantsQuestion 9 of 10

Which of these refrigerants is classified A1 (no flame propagation), not A2L?

Answer choices for question 9

Keyboard: A–D to choose · Enter to check

A2L, A3 & low-GWP refrigerantsQuestion 10 of 10

In the safety class "A2L," what does "2L" indicate?

Answer choices for question 10

Keyboard: A–D to choose · Enter to check

Open the full A2L, A3 & low-GWP topic practice

Frequently asked questions

Is R-454B flammable?

Yes. R-454B is A2L: lower toxicity and lower flammability. It is harder to ignite and burns more slowly than an A3 refrigerant, but it can burn, so follow the equipment and refrigerant safety instructions.

Can I put R-454B in an R-410A system?

No. EPA's SNAP listing allows R-454B for specified new equipment designed and identified for it; it is not a retrofit refrigerant for an existing R-410A system.

What color are A2L cylinders?

AHRI Guideline N recommends light green-gray (RAL 7044) containers for all refrigerants, with a red band on the shoulder or top for flammable refrigerants. Read the cylinder label; do not identify refrigerant by color alone.

Is R-32 better than R-454B?

Neither is universally better. Both are A2L; R-32 is a single-component refrigerant with GWP 675 and no glide, while R-454B is a blend with GWP 470 and a small glide. The equipment manufacturer chooses the refrigerant for the system.

Sources

Read what changed in the 2026 EPA 608 bank

A2L refrigerant list

Common A2L refrigerants
RefrigerantTypeTypical useGuides
R-32HFCNew residential split AC, heat pumps and mini-splitsGuide · P-T chart
R-454BHFC/HFO blendNew residential split AC and heat pumps (many manufacturers' R-410A successor)Guide · P-T chart
R-1234yfHFONew vehicle AC; component of blends such as R-454BP-T chart

In "A2L", A means lower toxicity and 2L means lower flammability: the "L" stands for a low burning velocity (EPA refrigerant safety).

Is there an A2L certification?

There is no separate EPA certification for A2L refrigerants; A2L knowledge is now part of the EPA 608 exam. Training organizations offer voluntary A2L safety certificates. See 2026 exam changes and all refrigerant types.