Quick answer: A2L refrigerants are lower-toxicity (A), lower-flammability (2L) refrigerants under ASHRAE Standard 34. R-32 and R-454B are replacing R-410A in new residential AC and heat pumps because of their lower GWP. They can burn, but are hard to ignite and burn slowly. EPA allows them only in new equipment designed for them, with red-marked service ports, and venting them is illegal under Section 608.
Last reviewed: November 24, 2026
ASHRAE 34 safety classes
| Part of class | Meaning | Examples |
|---|---|---|
| Toxicity letter A | Lower toxicity | R-410A, R-32, R-454B |
| Toxicity letter B | Higher toxicity | B1: R-123, R-514A; B2L: ammonia (R-717) |
| Class 1 | No flame propagation | A1: R-410A, R-134a, R-22 |
| Class 2L | Lower flammability; maximum burning velocity of 10 cm/s | A2L: R-32, R-454B, R-1234yf; B2L: ammonia (R-717) |
| Class 2 | Flammable | See the applicable refrigerant safety data and equipment labeling |
| Class 3 | Higher flammability | A3: R-290 (propane), R-600a (isobutane) |
ASHRAE’s class combines a toxicity letter and a flammability number. A2L refrigerants are lower-toxicity and lower-flammability, not nonflammable.
Compare common refrigerants and P-T values
These pressure values come from the site’s P-T chart data at 40°F, 75°F, and 100°F. For blends, each cell shows liquid/bubble pressure followed by vapor/dew pressure. Single-component refrigerants use one pressure value.
| Refrigerant | ASHRAE class | ODP | GWP | 40°F pressure (psig) | 75°F pressure (psig) | 100°F pressure (psig) |
|---|---|---|---|---|---|---|
| R-410A | A1 | 0 | 2,090 | 118.8 / 118.4 psig | 218.7 / 217.9 psig | 318.5 / 317.6 psig |
| R-32 | A2L | 0 | 675 | 121.0 psig | 223.2 psig | 325.7 psig |
| R-454B | A2L | 0 | 470 | 113.2 / 107.5 psig | 208.4 / 199.5 psig | 303.3 / 291.9 psig |
| R-1234yf | A2L | 0 | See EPA SNAP | 38.4 psig | 81.3 psig | 124.9 psig |
| R-290 | A3 | 0 | 3 | 63.9 psig | 119.5 psig | 173.9 psig |
| R-600a | A3 | 0 | See EPA SNAP | 11.9 psig | 34.5 psig | 57.9 psig |
EPA’s SNAP residential AC table lists GWP values of R-410A 2,090, R-32 675, R-454B 470, and R-290 3. For R-1234yf and R-600a, see EPA SNAP. These P-T values are provided for study and reference; confirm with the manufacturer for field work.
EPA SNAP use conditions for R-32 and R-454B
EPA’s May 6, 2021 SNAP rule lists these refrigerants for specified new residential and light commercial AC and heat-pump equipment, subject to use conditions.
- New equipment only: equipment must be designed and identified for that refrigerant; the listing does not authorize retrofitting an R-410A system.
- Safety standard: meet UL 60335-2-40, 3rd edition, including charge limits based on room size and the listed safeguards.
- Warnings: equipment must carry the required warning labels.
- Red service markings: use red PMS #185 or RAL 3020 at service ports and other places the refrigerant circuit can be opened. Markings extend at least 1 inch (25 mm) in both directions and must be replaced if removed.
A2L cylinders and recovery cylinders
- AHRI Guideline N recommends light green-gray (RAL 7044) for refrigerant containers generally and a red band on the shoulder or top for flammable refrigerants.
- Most A2L disposable cylinders use a left-hand-thread outlet and a resettable pressure relief valve instead of a rupture disc.
- AHRI Guideline K specifies left-hand threads for recovery cylinders holding flammable refrigerants.
- Always identify refrigerant by its label, not color alone.
Venting and recovery
R-32 and R-454B are non-exempt substitutes: knowingly venting them during service is prohibited, and recovery equipment must be certified for the refrigerant and appliance. Section 608 exemptions apply only to named substitutes in specific end uses.
For example, R-600a is exempt in household refrigerators and freezers, and R-290 is exempt in listed end uses such as self-contained room ACs and stand-alone retail food units. Those exemptions do not authorize R-290 in split-system central AC.
A2L/A3 field practices
- Ventilate the work area and keep ignition sources away.
- Recover refrigerant before brazing, then purge with dry nitrogen. Never use oxygen to pressure-test or purge a refrigeration system.
- Charge zeotropic blends such as R-454B as liquid to avoid changing blend composition.
- For blend measurements, use dew pressure for superheat and bubble pressure for subcooling.
Related tools: superheat calculator and subcooling calculator.
Free 10-question A2L and A3 quiz
Open the full A2L, A3 & low-GWP topic practice
Frequently asked questions
Is R-454B flammable?
Yes. R-454B is A2L: lower toxicity and lower flammability. It is harder to ignite and burns more slowly than an A3 refrigerant, but it can burn, so follow the equipment and refrigerant safety instructions.
Can I put R-454B in an R-410A system?
No. EPA's SNAP listing allows R-454B for specified new equipment designed and identified for it; it is not a retrofit refrigerant for an existing R-410A system.
What color are A2L cylinders?
AHRI Guideline N recommends light green-gray (RAL 7044) containers for all refrigerants, with a red band on the shoulder or top for flammable refrigerants. Read the cylinder label; do not identify refrigerant by color alone.
Is R-32 better than R-454B?
Neither is universally better. Both are A2L; R-32 is a single-component refrigerant with GWP 675 and no glide, while R-454B is a blend with GWP 470 and a small glide. The equipment manufacturer chooses the refrigerant for the system.
Sources
- EPA — Refrigerant Safety (ASHRAE Standard 34 classes)
- EPA SNAP — Residential and light commercial AC and heat pumps
- EPA SNAP Rule 23, 86 FR 24444
- 40 CFR 82.154 — Prohibitions
- AHRI Guideline N-2017 — Refrigerant container colors
- Arkema Forane — A2L vs. A1 cylinders
- AHRI Guideline K-2024 — Recovery cylinders
- 40 CFR 82.152 — Definitions
- EPA — Section 608 Test Topics