Quick answer: CFCs and HCFCs contain chlorine, which destroys stratospheric ozone, so they have been phased out under the Montreal Protocol and the Clean Air Act. HFCs and HFOs contain no chlorine, so their ozone depletion potential (ODP) is zero, but many HFCs have a high global warming potential (GWP) and are being phased down under the AIM Act.
By the TradeCert Prep editorial team · Last reviewed: November 26, 2026 · How we research and check our content
Refrigerant families compared
| Family | Contains chlorine? | Examples (ODP / GWP) | Status |
|---|---|---|---|
| CFC | Yes | R-12 (1 / 10,900) | Production phased out |
| HCFC | Yes | R-22 (0.055 / 1,810); R-123 (0.02 / 77) | R-22 ended 2020; all HCFCs end 2030 |
| HFC | No | R-410A (0 / 2,088); R-32 (0 / 675); R-134a (0 / 1,430); R-404A (0 / 3,922); R-407C (0 / 1,774) | Phasing down to 15% of baseline by 2036 |
| HFO and HFO blends | No | R-454B (0 / 465); R-1234yf (0 / 1) | Growing use in new equipment |
| Hydrocarbons | No | R-290 (propane) (0 / 3.3); R-600a (isobutane) (0 / 1) | Only in equipment designed for them |
ODP for CFCs and HCFCs from the Montreal Protocol and GWP from IPCC AR4, both as listed by EPA; HFC, HFO and hydrocarbon GWPs from EPA's Technology Transitions table.
ODP vs GWP
Ozone depletion potential compares a substance's damage to the ozone layer with CFC-11 (ODP 1). Chlorine is the culprit, so only chlorine-containing refrigerants have an ODP above zero. Global warming potential compares how much heat a gas traps over 100 years with CO2 (GWP 1). R-410A's GWP of 2,088 means one pound traps about as much heat as 2,088 pounds of CO2.
Phaseout timeline
| When | What |
|---|---|
| 1987 | Montreal Protocol signed to phase out ozone-depleting substances |
| 1990 | Clean Air Act amendments (Title VI) set the U.S. phaseout and refrigerant management rules |
| 2010 | No R-22 production for new equipment (EPA) |
| January 1, 2020 | No R-22 production or import (EPA) |
| 2024–2028 | HFC production and import capped at 60% of baseline (EPA) |
| January 1, 2025 | New residential and light-commercial AC systems limited to GWP 700 (EPA) |
| 2030 | No production or import of any HCFC (EPA) |
| 2036 | HFC cap reaches 15% of baseline (EPA) |
Study this for the exam
The free EPA 608 lesson on ozone depletion and environmental impact covers the exact points Core tests.
On the EPA 608 exam
Identifying CFCs, HCFCs and HFCs and ranking their ozone impact is one of the first things Core tests.
Test yourself: 6 Core questions on ozone depletion
These are the first Core questions
Ozone depletion and refrigerant families open the Core section. Test yourself free.
Frequently asked questions
What are CFC, HCFC and HFC refrigerants?
CFCs (chlorofluorocarbons, e.g. R-12) contain chlorine and have the highest ozone depletion potential. HCFCs (e.g. R-22) contain hydrogen and less chlorine, so they deplete less. HFCs (e.g. R-410A, R-134a) contain no chlorine, so ODP is zero, but many have high GWP.
Are HFCs being phased out?
They are being phased down, not banned outright: U.S. HFC production and import is capped at a falling share of a baseline, reaching 15% from 2036, and new equipment in many sectors must use lower-GWP refrigerants.
What oil is used with HFC refrigerants?
HFCs generally use ester (POE) lubricants because they don't mix well with the mineral oil used with CFCs and many HCFCs.
Which refrigerants are no longer produced?
CFCs such as R-12, and HCFC-22 (R-22), whose production and import ended in the U.S. on January 1, 2020. All HCFC production ends in 2030.
Sources
- EPA — Ozone-Depleting Substances (ODP and AR4 GWP values, updated April 9, 2026)
- EPA — Technology Transitions GWP Reference Table (updated April 2, 2026)
- EPA — Phaseout of Class II Ozone-Depleting Substances (updated April 1, 2026)
- EPA — Phaseout of Class I Ozone-Depleting Substances
- EPA — Frequent Questions on the Phasedown of HFCs
- EPA — Technology Transitions HFC Restrictions by Sector (updated August 28, 2026)
- EPA — Section 608 Test Topics (updated November 24, 2026)