Skip to content
TradeCert Prep
Pressure–temperature reference

R-410A Pressure Temperature Chart (°F and °C)

Quick answer: At 75°F, R-410A is about 218.7 psig liquid/bubble and 217.9 psig vapor/dew. The full chart shows the database values every 5°F from -40°F to 150°F. Values are gauge pressure at sea level; use bubble for liquid-side subcooling and dew for vapor-side superheat. Confirm charging targets with the equipment manufacturer.

Last reviewed: November 24, 2026

Field lookup

Quick pressure and temperature lookup

The lookup linearly interpolates between the nearest published table points. Choose bubble for liquid/subcooling or dew for vapor/superheat.

Liquid (bubble)—Use for subcooling (liquid line)
Vapor (dew)—Use for superheat (suction line)

Jump to

Look up R-410A saturation pressure by temperature or estimate saturation temperature from pressure. Values are gauge pressure (psig) at sea level.

Values computed with CoolProp 8.1.0 (open-source thermophysical property library; Bell et al., Ind. Eng. Chem. Res. 2014) using Helmholtz-energy equations of state; blends modeled from their nominal ASHRAE 34 mass compositions. A few points near the top of the range were interpolated. For field work, confirm against the refrigerant manufacturer's PT chart.

Download CSV

R-410A saturation table

Saturation pressure values for R-410A. Negative gauge pressures are shown as inches of mercury vacuum.
Temp °FTemp °CLiquid / bubble (psig)Vapor / dew (psig)
-40 °F-40.0 °C10.8 psig10.7 psig
-35 °F-37.2 °C14.1 psig14.0 psig
-30 °F-34.4 °C17.8 psig17.7 psig
-25 °F-31.7 °C21.9 psig21.8 psig
-20 °F-28.9 °C26.3 psig26.2 psig
-15 °F-26.1 °C31.2 psig31.0 psig
-10 °F-23.3 °C36.5 psig36.3 psig
-5 °F-20.6 °C42.2 psig42.0 psig
0 °F-17.8 °C48.4 psig48.2 psig
5 °F-15.0 °C55.2 psig54.9 psig
10 °F-12.2 °C62.4 psig62.2 psig
15 °F-9.4 °C70.3 psig70.0 psig
20 °F-6.7 °C78.7 psig78.4 psig
25 °F-3.9 °C87.7 psig87.4 psig
30 °F-1.1 °C97.4 psig97.0 psig
35 °F1.7 °C107.7 psig107.3 psig
40 °F4.4 °C118.8 psig118.4 psig
45 °F7.2 °C130.6 psig130.1 psig
50 °F10.0 °C143.2 psig142.6 psig
55 °F12.8 °C156.5 psig156.0 psig
60 °F15.6 °C170.7 psig170.1 psig
65 °F18.3 °C185.8 psig185.1 psig
70 °F21.1 °C201.8 psig201.1 psig
75 °F23.9 °C218.7 psig217.9 psig
80 °F26.7 °C236.5 psig235.8 psig
85 °F29.4 °C255.4 psig254.6 psig
90 °F32.2 °C275.4 psig274.5 psig
95 °F35.0 °C296.4 psig295.5 psig
100 °F37.8 °C318.5 psig317.6 psig
105 °F40.6 °C341.9 psig340.9 psig
110 °F43.3 °C366.5 psig365.4 psig
115 °F46.1 °C392.3 psig391.2 psig
120 °F48.9 °C419.4 psig418.3 psig
125 °F51.7 °C447.9 psig446.8 psig
130 °F54.4 °C477.9 psig476.8 psig
135 °F57.2 °C509.4 psig508.3 psig
140 °F60.0 °C542.5 psig541.4 psig
145 °F62.8 °C577.3 psig576.3 psig
150 °F65.6 °C613.9 psig613.0 psig

R-410A chart FAQs

What is the pressure of R-410A at 75°F?

At 75°F, R-410A is approximately 218.7 psig liquid/bubble and 217.9 psig vapor/dew.

What is the boiling temperature of R-410A at 0 psig?

Zero gauge pressure is outside the published temperature range for R-410A.

Does R-410A have temperature glide?

Yes. At 75°F, the listed liquid/bubble and vapor/dew pressures differ by approximately 0.8 psi. Use bubble for liquid/subcooling and dew for vapor/superheat.

What is R-410A used for?

Residential split AC and heat pumps installed from about 2010 to 2024. R-410A is a HFC blend with ASHRAE safety class A1 and a 100-year GWP of 2,088. New residential and light-commercial AC systems are limited to GWP 700 from January 1, 2025 (systems whose components were all made before then are exempt); servicing existing equipment is not restricted.

Cite this chart: R-410A pressure-temperature chart, TradeCert Prep, computed with CoolProp 8.1.0, retrieved November 26, 2026. License CC BY 4.0.

More about R-410A

R-410A is a HFC blend (R-32/R-125, 50/50 by mass), ASHRAE safety class A1, with a 100-year GWP of 2,088 and an ODP of 0. Typical use: residential split AC and heat pumps installed from about 2010 to 2024. New residential and light-commercial AC systems are limited to GWP 700 from January 1, 2025 (systems whose components were all made before then are exempt); servicing existing equipment is not restricted.

Status, replacements, safety and who can buy it: read the R-410A refrigerant guide. Compare every refrigerant's class, safety and GWP in types of refrigerant, or see how the refrigeration cycle works.