Quick answer: The refrigeration cycle moves heat from inside to outside by changing refrigerant between liquid and vapor. In the evaporator, low-pressure liquid boils and absorbs heat. The compressor raises the vapor's pressure and temperature. In the condenser, the vapor rejects heat and condenses to liquid. The metering device drops the pressure, and the cycle repeats.
By the TradeCert Prep editorial team · Last reviewed: November 26, 2026 · How we research and check our content
What happens in each component
| Component | Refrigerant enters as | Leaves as | Side | Job |
|---|---|---|---|---|
| Compressor | Low-pressure, superheated vapor | High-pressure, high-temperature vapor | Low → high | Pumps refrigerant and raises its pressure so it can condense at outdoor temperatures |
| Condenser | High-pressure, superheated vapor | High-pressure, subcooled liquid | High | Rejects heat to the outdoor air or water; the vapor condenses |
| Metering device | High-pressure liquid | Low-pressure liquid and flash vapor | High → low | Drops pressure and controls flow into the evaporator |
| Evaporator | Low-pressure liquid and vapor | Low-pressure, superheated vapor | Low | Absorbs heat from the indoor air; the liquid boils |
Knowing the refrigerant's state and pressure at each point is an EPA 608 Core topic (EPA test topics).
Why pressure and temperature move together
Wherever liquid and vapor are both present, in the evaporator and condenser, the refrigerant is saturated: its temperature is fixed by its pressure. That relationship is what a pressure-temperature (P-T) chart lists, and it's why gauges let you work out what's happening inside a sealed system. Blends such as R-454B have glide, so their charts list separate bubble (liquid) and dew (vapor) values.
Worked example: an R-410A system on gauges
Low-side gauges are blue, high-side red, and the center hose yellow (EPA test topics). Using our R-410A data:
- An evaporator boiling at 40°F reads about 118.4 psig on the low side (dew value).
- A condenser condensing at 110°F reads about 366.5 psig on the high side (bubble value).
- If the suction line measures 50°F, the superheat is 50 − 40 = 10°F.
- If the liquid line measures 100°F, the subcooling is 110 − 100 = 10°F.
Run your own numbers with the superheat calculator and subcooling calculator. Gauges read psig; add 14.7 for absolute pressure (psig to psia converter). These are illustrations, not target values: charging targets come from the equipment manufacturer.
On the EPA 608 exam
The refrigeration cycle, refrigerant states and gauges are tested in EPA 608 Core.
Test yourself: 6 Core questions on the cycle and gauges
Turn the cycle into exam points
Core questions on states, pressures and gauges are some of the easiest to get right once the cycle clicks. Practice free.
Frequently asked questions
What are the four main parts of the refrigeration cycle?
The compressor, condenser, metering device (expansion valve, piston or capillary tube) and evaporator. The refrigerant absorbs heat in the evaporator and rejects it in the condenser.
Where in the cycle is the refrigerant hottest?
In the discharge line leaving the compressor, where it is a high-pressure, superheated vapor.
What is superheat?
The temperature of the vapor above its saturation (boiling) temperature at the same pressure, usually measured at the suction line. It shows how completely the evaporator boiled off the liquid.
What is subcooling?
The temperature of the liquid below its saturation (condensing) temperature at the same pressure, usually measured at the liquid line. It shows how much liquid has backed up in the condenser.