Skip to content
TradeCert Prep
Pressure–temperature reference

R-22 Pressure Temperature Chart (°F and °C)

Quick answer: At 75°F, R-22 is about 132.2 psig. The full chart shows the database values every 5°F from -40°F to 150°F. Values are gauge pressure at sea level; use bubble for liquid-side subcooling and dew for vapor-side superheat. Confirm charging targets with the equipment manufacturer.

Last reviewed: November 24, 2026

Field lookup

Quick pressure and temperature lookup

The lookup linearly interpolates between the nearest published table points. Choose bubble for liquid/subcooling or dew for vapor/superheat.

Saturation—Single-component: one pressure for liquid and vapor

Jump to

Look up R-22 saturation pressure by temperature or estimate saturation temperature from pressure. Values are gauge pressure (psig) at sea level.

Values computed with CoolProp 8.1.0 (open-source thermophysical property library; Bell et al., Ind. Eng. Chem. Res. 2014) using Helmholtz-energy equations of state; blends modeled from their nominal ASHRAE 34 mass compositions. A few points near the top of the range were interpolated. For field work, confirm against the refrigerant manufacturer's PT chart.

Download CSV

R-22 saturation table

Saturation pressure values for R-22. Negative gauge pressures are shown as inches of mercury vacuum.
Temp °FTemp °CSaturation (psig)
-40 °F-40.0 °C0.6 psig
-35 °F-37.2 °C2.6 psig
-30 °F-34.4 °C4.9 psig
-25 °F-31.7 °C7.4 psig
-20 °F-28.9 °C10.2 psig
-15 °F-26.1 °C13.2 psig
-10 °F-23.3 °C16.5 psig
-5 °F-20.6 °C20.1 psig
0 °F-17.8 °C24.0 psig
5 °F-15.0 °C28.3 psig
10 °F-12.2 °C32.8 psig
15 °F-9.4 °C37.8 psig
20 °F-6.7 °C43.1 psig
25 °F-3.9 °C48.8 psig
30 °F-1.1 °C55.0 psig
35 °F1.7 °C61.5 psig
40 °F4.4 °C68.6 psig
45 °F7.2 °C76.1 psig
50 °F10.0 °C84.1 psig
55 °F12.8 °C92.6 psig
60 °F15.6 °C101.6 psig
65 °F18.3 °C111.2 psig
70 °F21.1 °C121.4 psig
75 °F23.9 °C132.2 psig
80 °F26.7 °C143.6 psig
85 °F29.4 °C155.7 psig
90 °F32.2 °C168.4 psig
95 °F35.0 °C181.8 psig
100 °F37.8 °C195.9 psig
105 °F40.6 °C210.8 psig
110 °F43.3 °C226.4 psig
115 °F46.1 °C242.8 psig
120 °F48.9 °C260.0 psig
125 °F51.7 °C278.0 psig
130 °F54.4 °C296.9 psig
135 °F57.2 °C316.7 psig
140 °F60.0 °C337.4 psig
145 °F62.8 °C359.0 psig
150 °F65.6 °C381.7 psig

R-22 chart FAQs

What is the pressure of R-22 at 75°F?

At 75°F, R-22 is approximately 132.2 psig.

What is the boiling temperature of R-22 at 0 psig?

Zero gauge pressure is outside the published temperature range for R-22.

Does R-22 have temperature glide?

R-22 is single-component in this chart, so its bubble and dew pressures are the same at each listed temperature.

What is R-22 used for?

Residential AC and heat pumps built before 2010, older commercial systems. R-22 is a HCFC with ASHRAE safety class A1 and a 100-year GWP of 1,810. Production and import ended January 1, 2020; equipment is serviced from existing, recovered and reclaimed supply.

Cite this chart: R-22 pressure-temperature chart, TradeCert Prep, computed with CoolProp 8.1.0, retrieved November 26, 2026. License CC BY 4.0.

More about R-22

R-22 is a HCFC, ASHRAE safety class A1, with a 100-year GWP of 1,810 and an ODP of 0.055. Typical use: residential AC and heat pumps built before 2010, older commercial systems. Production and import ended January 1, 2020; equipment is serviced from existing, recovered and reclaimed supply.

Status, replacements, safety and who can buy it: read the R-22 refrigerant guide. Compare every refrigerant's class, safety and GWP in types of refrigerant, or see how the refrigeration cycle works.