Quick answer: R-454B is a blend of R-32 and R-1234yf (68.9/31.1 by mass) used in many new residential air conditioners and heat pumps as the successor to R-410A. It is A2L (lower flammability), has a GWP of 465 and zero ozone depletion, and EPA SNAP lists it for new equipment only, not as a retrofit for R-410A systems.
By the TradeCert Prep editorial team · Last reviewed: November 26, 2026 · How we research and check our content
| Type | HFC/HFO blend — R-32/R-1234yf, 68.9/31.1 by mass |
|---|---|
| ASHRAE safety class | A2L |
| Global warming potential (100-year) | 465 (EPA) |
| Ozone depletion potential | 0 (EPA) |
| Typical equipment | New residential split AC and heat pumps (many manufacturers' R-410A successor) |
| Regulatory status | SNAP-acceptable (with use conditions) for new residential and light-commercial AC; not listed for retrofits. |
R-454B pressures and glide
| Temperature | Liquid (bubble) | Vapor (dew) |
|---|---|---|
| 65°F | 177.1 | 169.2 |
| 75°F | 208.4 | 199.5 |
| 85°F | 243.4 | 233.5 |
| 95°F | 282.3 | 271.4 |
From our P-T dataset. A system that has been off long enough to reach ambient temperature should read close to these values (a "standing pressure"); see the full R-454B P-T chart for every temperature.
Because R-454B is a zeotropic blend, it boils over a small temperature range at a given pressure: the bubble (liquid) and dew (vapor) pressures differ. From our data, the glide at a 40°F bubble point is about 2.6°F. Use dew values for superheat and bubble values for subcooling.
Why manufacturers moved to R-454B
From January 1, 2025, new residential and light-commercial AC and heat pump systems must use a refrigerant with GWP of 700 or less (EPA). R-410A (GWP 2,088) doesn't qualify; R-454B (465) does, at operating pressures close to R-410A's. See R-410A vs R-454B vs R-32.
Servicing R-454B equipment
- It's A2L: use A2L-rated tools and recovery equipment and follow the manufacturer's instructions (A2L guide).
- It's a blend: charge as liquid per the manufacturer, since blend components can fractionate (EPA test topics).
- Never mix refrigerants or top off with R-410A or R-32.
- Buying it requires EPA 608 certification (EPA sales restriction).
On the EPA 608 exam
A2L refrigerants such as R-454B were added to the EPA 608 test bank in 2026.
Test yourself: 6 EPA 608 practice questions
Get certified to work on R-454B systems
See how you'd score on the updated EPA 608 Core section, free.
Frequently asked questions
What is the new HVAC refrigerant?
New residential AC systems must use a refrigerant with GWP of 700 or less from 2025; R-454B and R-32 are the A2L refrigerants EPA SNAP lists for this equipment. Both are A2L refrigerants.
Should I use R-32 or R-454B?
You don't choose: the equipment is designed for one of them and must be charged with that refrigerant. R-454B has the lower GWP (465 vs 675) and a small glide; R-32 is a single component with no glide.
Can you mix R-32 and R-454B?
No. Never mix refrigerants: mixed refrigerant can be hard or impossible to reclaim. Charge only the refrigerant on the nameplate.
Can R-454B replace R-410A in an existing system?
No. EPA SNAP lists R-454B for new equipment designed for it, not as a retrofit for R-410A equipment.
Sources
- EPA — Technology Transitions GWP Reference Table (updated April 2, 2026)
- EPA SNAP — Substitutes in Residential and Light Commercial AC and Heat Pumps (updated March 19, 2026)
- EPA — Technology Transitions HFC Restrictions by Sector (updated August 28, 2026)
- EPA — Refrigerant Sales Restriction (updated March 23, 2026)
- EPA — Section 608 Test Topics (updated November 24, 2026)
- TradeCert Prep P-T data (computed with CoolProp 8.1.0; see methodology)