EPA 608 glossary
102 terms from the rules and the test, in plain language. Every definition cites its source.
A
- A1
- ASHRAE Standard 34 class for lower-toxicity refrigerants with no flame propagation, such as R-22, R-134a and R-410A.
- Source: EPA — Refrigerant Safety (ASHRAE Standard 34 classes)
- A2L
- A2L means lower toxicity and lower flammability under ASHRAE Standard 34.
- Source: EPA — Refrigerant Safety (ASHRAE Standard 34 classes)
- A3
- A3 is ASHRAE Standard 34's higher-flammability class; hydrocarbons such as propane (R-290) are A3. An A2L refrigerant is harder to ignite and burns more slowly than an A3 refrigerant.
- Source: EPA — Refrigerant Safety (ASHRAE Standard 34 classes)
- AHRI Standard 700
- The purity standard for reclaimed refrigerant; recovered refrigerant that changes ownership must be reclaimed to AHRI 700 by an EPA-certified reclaimer.
- Source: EPA – Stationary Refrigeration Service Practice Requirements
- AIM Act
- A 2020 law, separate from the Clean Air Act, under which EPA phases down HFCs and sets HFC leak-repair and technology-transition rules (40 CFR Part 84).
- Source: 40 CFR Part 84 (AIM Act HFC rules)
- ASHRAE Standard 34
- The standard that assigns refrigerant safety classes by toxicity and flammability, such as A1, A2L and A3.
- Source: EPA — Refrigerant Safety (ASHRAE Standard 34 classes)
- Accumulator
- An accumulator sits in the suction line and traps liquid refrigerant (and returns oil slowly) so liquid doesn't flood the compressor.
- Source: EPA – Section 608 Test Topics
- Apprentice
- An uncertified person may work as an apprentice only while closely and continually supervised by a certified technician.
- Source: EPA – Section 608 Technician Certification Requirements
- Automatic leak detection
- Required on commercial refrigeration and IPR appliances with 1,500 lb or more of HFC: at installation for systems installed from Jan 1, 2026, and by Jan 1, 2027 for systems installed from 2017 through 2025.
- Source: 40 CFR 84.108
- Azeotrope
- A refrigerant blend whose components boil together at one temperature, so it behaves like a single substance with no glide and does not fractionate significantly. Example: R-502.
- Source: EPA – Section 608 Test Topics
B
- Bubble point
- The liquid side of a blend's pressure-temperature curve. Use bubble values for liquid-side subcooling.
- Source: TradeCert Prep P-T chart methodology
C
- CFC
- Chlorofluorocarbon refrigerants such as R-12. CFCs have the highest ODP, HCFCs have a much lower ODP, and HFCs have an ODP of zero because they contain no chlorine.
- Source: EPA – Section 608 Test Topics
- Certifying organization
- EPA does not issue certification cards; EPA-approved certifying organizations give the test and issue the card.
- Source: 40 CFR Part 82, Subpart F, Appendix D
- Charging a chiller
- When charging a chiller, charge refrigerant as vapor before liquid.
- Source: EPA – Section 608
- Chronic leaker
- An appliance leaking 125% or more of its full charge in a calendar year. It must be reported to EPA by March 1 of the following year.
- Source: 40 CFR 82.157
- Comfort cooling
- Air-conditioning appliances used to cool people, such as building chillers. Their leak rate trigger is 10% for appliances with 50 lb or more of ozone-depleting refrigerant (40 CFR 82.157); HFC/substitute appliances with 15 lb or more use the same triggers under 40 CFR 84.106 since Jan 1, 2026.
- Source: 40 CFR 82.157
- Commercial refrigeration
- Refrigeration appliances used in retail food and cold storage. Their leak rate trigger is 20% for appliances with 50 lb or more of ozone-depleting refrigerant (40 CFR 82.157); HFC/substitute appliances with 15 lb or more use the same triggers under 40 CFR 84.106 since Jan 1, 2026.
- Source: 40 CFR 82.157
- Compressor
- The compressor raises refrigerant pressure and temperature, discharging a high-pressure, high-temperature (superheated) vapor to the condenser.
- Source: EPA – Section 608 Test Topics
- Condenser
- The condenser rejects heat to air or water, condensing high-pressure vapor into high-pressure liquid.
- Source: EPA – Section 608 Test Topics
- Contaminated refrigerant
- Contaminated refrigerant should not be mixed with good refrigerant; it must be recovered and sent for reclamation or destruction if it can't be reclaimed.
- Source: EPA – Refrigerant Reclamation Requirements
- Core section
- The 25-question section included in every Type I, Type II, Type III or Universal exam, covering rules, environment, recovery, safety and shipping.
- Source: 40 CFR Part 82, Subpart F, Appendix D
- Cylinder color (flammable refrigerants)
- AHRI Guideline N recommends light green-gray (RAL 7044) containers for all refrigerants, with a red band on the shoulder or top for flammable refrigerants. Read the label; do not identify refrigerant by color alone.
- Source: AHRI Guideline N-2017 — Refrigerant container colors
D
- DOT hazard class 2.2
- Most common A1 fluorocarbon refrigerants such as R-22, R-134a and R-410A ship as DOT Class 2.2, non-flammable gas.
- Source: EPA – Section 608 Test Topics
- Dehydration
- EPA's Core topics include the need to evacuate the system to eliminate air and moisture at the end of service, since both cause acids, high head pressure and poor performance.
- Source: EPA – Section 608 Test Topics
- Dew point
- The vapor side of a blend's pressure-temperature curve. Use dew values for vapor-side superheat.
- Source: TradeCert Prep P-T chart methodology
- Disposal
- Under the safe disposal rule, the final person in the disposal chain must either recover remaining refrigerant or verify, with a signed statement or contract, that it was properly recovered.
- Source: EPA – Stationary Refrigeration Safe Disposal Requirements
E
- Electronic leak detector
- Electronic detectors need time to sense trace gas, so probe slowly and close to joints. Because refrigerant is heavier than air, check below fittings too.
- Source: EPA – Section 608 Test Topics
- Energizing a compressor under vacuum
- EPA's Type II safety topic: don't energize hermetic compressors under vacuum, because motor winding insulation can break down and short.
- Source: EPA – Section 608 Test Topics
- Equipment certification
- Except for equipment manufactured before November 15, 1993, recovery or recycling equipment must be certified by an EPA-approved testing organization.
- Source: EPA – Stationary Refrigeration Service Practice Requirements
- Evacuation
- Pulling a system into a vacuum to remove refrigerant, air and moisture. EPA's table sets required evacuation levels by appliance type, charge size and recovery-equipment date.
- Source: 40 CFR 82.156(a), Table 1
- Evaporator
- The low-pressure heat exchanger where liquid refrigerant boils and absorbs heat from the air or water being cooled; low-pressure vapor leaves for the compressor.
- Source: EPA – Section 608 Test Topics
F
- Fractionation
- The tendency of different components of a blend to leak or vaporize at different rates, changing the composition of what remains in the system.
- Source: EPA – Section 608 Test Topics
- Full charge
- The amount of refrigerant an appliance holds when it is fully charged. Leak repair rules apply by full charge, such as 50 lb or more of ozone-depleting refrigerant.
- Source: 40 CFR 82.157
G
- Global warming potential (GWP)
- A measure of a refrigerant's climate impact relative to CO2. The EPA SNAP residential AC table lists GWP values of 2,090 for R-410A, 675 for R-32, 470 for R-454B, and 3 for R-290.
- Source: EPA SNAP — Residential and light commercial AC and heat pumps
H
- HCFC
- Hydrochlorofluorocarbon refrigerants such as R-22 and R-123. They contain chlorine, so they deplete ozone, but much less than CFCs.
- Source: EPA – Section 608 Test Topics
- HFC
- HFCs contain hydrogen, fluorine and carbon but no chlorine or bromine, so their ODP is 0. Some HFCs do have high global warming potential.
- Source: EPA – Section 608 Test Topics
- HFC leak repair rule (Part 84)
- Since January 1, 2026, appliances with 15 lb or more of an HFC or a substitute with GWP above 53 follow leak repair rules in 40 CFR 84.106, with the same 30% / 20% / 10% triggers.
- Source: 40 CFR 84.106
- HFO
- R-1234yf is a hydrofluoroolefin: hydrogen, fluorine and carbon with a double bond. It has no chlorine, so its ODP is 0, and it has a very low GWP.
- Source: EPA – Section 608 Test Topics
- High-pressure appliance
- 40 CFR 82.152: high-pressure appliance = liquid phase saturation pressure between 170 psia and 355 psia at 104°F (e.g. R-22, R-407C, R-410A).
- Source: 40 CFR 82.152 – Definitions
I
- Inches of mercury vacuum (in Hg)
- Evacuation levels are measured in inches of Hg vacuum relative to standard atmospheric pressure (29.9 in Hg).
- Source: 40 CFR 82.156(a), Table 1
- Industrial process refrigeration (IPR)
- Refrigeration used in industrial processes. Its leak rate trigger is 30% for appliances with 50 lb or more of ozone-depleting refrigerant (40 CFR 82.157); HFC/substitute appliances with 15 lb or more use the same trigger under 40 CFR 84.106 since Jan 1, 2026. Repairs needing an industrial process shutdown get 120 days instead of 30.
- Source: 40 CFR 82.157
L
- Leak rate
- The rate at which an appliance loses refrigerant, calculated each time refrigerant is added. Repair is required when it exceeds the trigger for the appliance type.
- Source: 40 CFR 82.157
- Leak rate trigger
- Industrial process refrigeration 30%, commercial refrigeration 20%, and comfort cooling and other appliances 10%, for appliances with 50 lb or more of ozone-depleting refrigerant.
- Source: 40 CFR 82.157
- Leak testing (low-pressure)
- Pressurize for leak testing to no more than 10 psig; the rupture disc relieves at 15 psig.
- Source: EPA – Section 608
- Low-pressure appliance
- An appliance that uses a refrigerant such as R-11, R-123, R-113 or R-245fa. Low-pressure appliances are evacuated to 25 mm Hg absolute.
- Source: 40 CFR 82.156(a), Table 1
M
- MVAC-like appliance
- Small appliances, MVACs and MVAC-like appliances are not covered by the evacuation levels table; MVAC-like appliances being disposed of are evacuated per 40 CFR part 82 subpart B or to 102 mm Hg vacuum or lower.
- Source: 40 CFR 82.156(c)-(d)
- Mail-in Type I test
- An approved program may offer Type I as a mail-in, open-book test. It requires 84% to pass and cannot be used toward Universal certification.
- Source: 40 CFR Part 82, Subpart F, Appendix D
- Major repair (low-pressure)
- Removing the compressor, condenser, evaporator or auxiliary heat exchange coil is a major repair under 40 CFR 82.152.
- Source: 40 CFR 82.152 – Definitions
- Medium-pressure appliance
- An appliance that uses a refrigerant such as R-12, R-134a, R-500, R-114 or R-124, as listed in EPA's required evacuation levels table.
- Source: 40 CFR 82.156(a), Table 1
- Metering device
- High-pressure liquid from the condenser (or receiver) feeds the metering device, which drops the pressure before the evaporator.
- Source: EPA – Section 608 Test Topics
- Montreal Protocol
- The international treaty that controls the phaseout of ozone-depleting substance production and use.
- Source: EPA – International Actions: The Montreal Protocol
N
- Nitrogen
- EPA's topics require a pressure regulator and a pressure relief valve when using nitrogen, since a full nitrogen cylinder holds very high pressure.
- Source: EPA – Section 608 Test Topics
- Non-condensables
- Gases such as air that do not condense in the condenser; they take up condenser space and raise head pressure.
- Source: EPA – Section 608 Test Topics
O
- Oil change (low-pressure)
- Change oil only when the system is at 5 psig or less. Heat the oil to about 130°F to drive off dissolved refrigerant.
- Source: EPA – Section 608
- Ozone depletion potential (ODP)
- CFCs have the highest ODP, HCFCs have a much lower ODP, and HFCs have an ODP of zero because they contain no chlorine.
- Source: EPA – Section 608 Test Topics
P
- Personal protective equipment (PPE)
- EPA lists gloves and goggles as PPE for refrigerant handling, and a self-contained breathing apparatus (SCBA) in extreme cases such as a large release.
- Source: EPA – Section 608 Test Topics
- Phosgene
- At high temperatures, CFC and HCFC refrigerants can decompose into toxic and corrosive products such as hydrochloric acid, hydrofluoric acid and phosgene.
- Source: EPA – Section 608 Test Topics
- Purge unit
- A device on low-pressure systems that removes non-condensables (air and moisture), which leak in because these systems run partly below atmospheric pressure.
- Source: EPA – Section 608 Test Topics
- psig and psia
- At sea level, psia = psig + 14.696. Gauge pressure is measured relative to local atmosphere; absolute pressure is measured from a vacuum.
- Source: TradeCert Prep PSIG to PSIA converter
R
- R-123
- An HCFC refrigerant used in low-pressure appliances such as centrifugal chillers. Low-pressure appliances are evacuated to 25 mm Hg absolute.
- Source: 40 CFR 82.156(a), Table 1
- R-1234yf
- A low-GWP refrigerant. The HFC leak repair rule does not cover refrigerants with GWP of 53 or less such as R-1234yf or CO2.
- Source: 40 CFR 84.106
- R-22
- An HCFC refrigerant used in high-pressure appliances. As an ozone-depleting refrigerant, appliances with 50 lb or more of it fall under the 40 CFR 82.157 leak repair rule.
- Source: 40 CFR 82.157
- R-290 (propane)
- EPA's venting page notes propane (R-290) in stand-alone retail food refrigerators and freezers is exempt from the venting prohibition. It is highly flammable, so take precautions.
- Source: EPA – Prohibition on Venting Refrigerants
- R-32
- A single-component A2L refrigerant with GWP 675 and no glide, used in specified new equipment under EPA SNAP use conditions.
- Source: EPA SNAP — Residential and light commercial AC and heat pumps
- R-410A
- A widely used HFC blend for residential AC. The EPA SNAP residential AC table lists its GWP as 2,090.
- Source: EPA SNAP — Residential and light commercial AC and heat pumps
- R-454B
- A blended A2L refrigerant with GWP 470 and a small glide. It is not a retrofit refrigerant for an existing R-410A system.
- Source: EPA SNAP — Residential and light commercial AC and heat pumps
- Receiver
- Liquid collects in the receiver and liquid line, so liquid recovery is usually done at the liquid line or receiver king valve.
- Source: EPA – Section 608 Test Topics
- Reclamation
- Processing refrigerant to all the AHRI 700 specifications and verifying it by chemical analysis, usually at a certified reclamation facility.
- Source: EPA – Refrigerant Reclamation Requirements
- Recovery
- Recover means removing refrigerant in any condition from an appliance and storing it in an external container without necessarily testing or processing it.
- Source: EPA – Section 608 Test Topics
- Recovery cylinder
- Never fill a recovery cylinder beyond 80% of its capacity. Recovery cylinders are painted gray with a yellow top.
- Source: EPA – Section 608 Test Topics
- Recovery efficiency (small appliances)
- Recovery equipment made before Nov. 15, 1993 must recover 80% of the refrigerant; equipment made on or after that date must recover 90% when the compressor works, or 80% when it does not, or evacuate to 4 in Hg vacuum.
- Source: 40 CFR 82.156(b)
- Recovery equipment date (Nov. 15, 1993)
- EPA's evacuation table and small-appliance recovery rules depend on whether the recovery equipment was made before or on/after Nov. 15, 1993.
- Source: 40 CFR 82.156(a), Table 1
- Recycling
- Cleaning refrigerant for reuse by separating oil and passing it through devices such as filter-driers that reduce moisture, acidity and particulates, usually on site.
- Source: EPA – Section 608 Test Topics
- Refrigerant oil
- Substitute refrigerants are incompatible with many lubricants used with CFC and HCFC refrigerants (and vice versa), which affects oil return and system reliability.
- Source: EPA – Section 608 Test Topics
- Retrofit or retirement plan
- When an appliance will not be repaired, a retrofit or retirement plan is due within 30 days and the work completed within 1 year.
- Source: 40 CFR 82.157
- Rupture disc
- Low-pressure chillers have a rupture disc on the evaporator, typically 15 psig, to protect the shell from over-pressurization.
- Source: EPA – Section 608 Test Topics
S
- SCBA
- EPA's PPE list includes SCBA 'in extreme cases', such as entering a room with a large refrigerant leak and possible oxygen deprivation.
- Source: EPA – Section 608 Test Topics
- SNAP program
- EPA's Significant New Alternatives Policy program lists acceptable substitutes and their use conditions, such as the conditions for R-32 and R-454B in new equipment.
- Source: EPA SNAP — Residential and light commercial AC and heat pumps
- Sales restriction
- Only Section 608 certified technicians, or employers who show written evidence that they employ at least one, can buy refrigerant for stationary systems.
- Source: EPA – Refrigerant Sales Restriction
- Schrader valve
- Spring-loaded access valve; its core restricts flow, so removing cores (with a core-removal tool) speeds recovery.
- Source: EPA – Section 608 Test Topics
- Section 609
- Section 609 covers motor vehicle air-conditioning service for compensation. Section 608 covers stationary refrigeration and air-conditioning equipment.
- Source: EPA — Motor Vehicle Air Conditioning (Section 609)
- Self-contained recovery equipment
- Recovery equipment ('active') that can remove refrigerant from an appliance without the assistance of components in the appliance.
- Source: 40 CFR 82.152 – Definitions
- Signed statement (disposal)
- A disposal record that must include the name and address of the person who recovered the refrigerant and the date it was recovered.
- Source: EPA – Stationary Refrigeration Safe Disposal Requirements
- Small appliance
- A product factory-sealed with 5 lb or less of refrigerant. Small appliances are covered by Type I certification.
- Source: EPA – Section 608 Technician Certification Requirements
- Solderless access fitting
- EPA's Type I topics: technicians should remove solderless access fittings at the end of service because they can leak.
- Source: EPA – Section 608 Test Topics
- Standing pressure test
- A leak test in which the system is pressurized with nitrogen and isolated; a pressure drop over time at a steady temperature indicates a leak.
- Source: EPA – Section 608 Test Topics
- Stratospheric ozone
- When CFCs and HCFCs break down in the stratosphere under strong UV light they release chlorine atoms, and chlorine destroys ozone. Fluorine, carbon and hydrogen are not the ozone-depleting part.
- Source: EPA – Section 608 Test Topics
- Subcooling
- The number of degrees a liquid is cooled below its saturation temperature at the same pressure, typically measured at the condenser outlet or liquid line.
- Source: EPA – Section 608 Test Topics
- Superheat
- The number of degrees a vapor is heated above its saturation temperature at the same pressure.
- Source: EPA – Section 608 Test Topics
- System-dependent recovery equipment
- Recovery equipment ('passive') that relies on components of the appliance, such as its compressor or internal pressure, to recover refrigerant.
- Source: 40 CFR 82.152 – Definitions
T
- Temperature glide
- The change in evaporating and condensing temperature across a coil at constant pressure, because zeotropic blends boil and condense over a temperature range.
- Source: EPA – Section 608 Test Topics
- Type I certification
- Type I covers small appliances (factory-sealed with 5 lb or less of refrigerant).
- Source: EPA – Section 608 Technician Certification Requirements
- Type II certification
- Type II covers medium-, high- and very high-pressure appliances such as residential split systems and rooftop units.
- Source: EPA – Section 608 Technician Certification Requirements
- Type III certification
- Type III certification is for servicing or disposing of low-pressure appliances.
- Source: EPA – Section 608 Technician Certification Requirements
U
- Universal certification
- Universal covers Core and Types I, II and III: 100 questions, with the 70% passing mark in each section. It can also be earned by combining passing scores on the separate tests.
- Source: 40 CFR Part 82, Subpart F, Appendix D
V
- Vapor recovery (low-pressure)
- EPA lists the need to recover vapor in addition to liquid. In large, low-pressure vessels the remaining vapor still holds a significant amount of refrigerant.
- Source: EPA – Section 608 Test Topics
- Venting prohibition
- Section 608 regulations prohibit knowingly venting ozone-depleting refrigerants and their substitutes (such as HFCs) while maintaining, servicing, repairing or disposing of appliances. Only certain exempt substitutes and de minimis releases are allowed.
- Source: EPA – Prohibition on Venting Refrigerants
- Verification test
- After a leak repair, an initial and a follow-up verification test confirm that the repair worked.
- Source: 40 CFR 82.157
- Very high-pressure appliance
- An appliance that uses a refrigerant such as R-13, R-23 or R-503. EPA's evacuation table requires 0 in Hg vacuum for these with either age of recovery equipment.
- Source: 40 CFR 82.156(a), Table 1
W
- Water in tubes (chillers)
- A hydrostatic tube test, or testing the water circuit for refrigerant, helps determine whether a tube leak lets refrigerant and water mix.
- Source: EPA – Section 608 Test Topics
Z
- Zeotropic blend
- Because the components boil at different temperatures, zeotropic blends are charged as liquid (metered carefully to avoid flooding the compressor) so the charged composition matches the cylinder.
- Source: EPA – Section 608 Test Topics
Turn terms into points
Sign in for glossary cards and spaced-repetition reviews. Public practice tests need no signup.
Take a free practice test →