Quick answer: EPA SNAP lists several refrigerants as acceptable for retrofitting R-22 air conditioners, including R-407C, R-422B, R-422D, R-438A (MO99), R-421A, R-427A and R-417A. None is a true drop-in: each needs the maker's retrofit procedure and compatible oil. R-410A, R-32 and R-454B are not R-22 retrofits; they require new equipment.
By the TradeCert Prep editorial team · Last reviewed: November 26, 2026 · How we research and check our content
R-22 substitutes and their EPA status
| Refrigerant | Retrofit of existing R-22 equipment | New equipment | GWP (EPA) |
|---|---|---|---|
| R-407C | Acceptable | Acceptable | 1,774 |
| R-422B | Acceptable | Acceptable | Not in EPA table |
| R-422D | Acceptable | Acceptable | Not in EPA table |
| R-438A (MO99) | Acceptable | Acceptable | Not in EPA table |
| R-421A | Acceptable | Acceptable | Not in EPA table |
| R-427A | Acceptable | Not listed | Not in EPA table |
| R-417A | Acceptable | Acceptable | Not in EPA table |
| R-410A | Not listed | Acceptable | 2,088 |
| R-32 | Not listed | Acceptable with use conditions | 675 |
| R-454B | Not listed | Acceptable with use conditions | 465 |
| R-290 (propane) | Unacceptable | Acceptable with use conditions (self-contained room AC only) | 3.3 |
Source: EPA SNAP — Substitutes in Residential and Light Commercial AC and Heat Pumps (updated March 19, 2026); GWP from EPA's Technology Transitions table, which doesn't list every blend. A SNAP listing for new equipment doesn't override the 700 GWP limit for new AC systems installed from 2025 (EPA).
Why there's no true drop-in
EPA's test topics state plainly that no drop-in replacements exist. Substitute refrigerants often don't work with the mineral or alkylbenzene oil used with R-22, and blends can fractionate because their components leak at different rates (EPA test topics). Capacity, pressures and expansion device settings change too.
What a retrofit involves
- Recover all R-22 into a recovery cylinder; never vent it (how to recover refrigerant).
- Follow the substitute maker's retrofit guide for oil, seals, filter-drier and expansion device.
- Evacuate to remove air and moisture (evacuation and dehydration), then charge the new refrigerant as liquid if it's a blend.
- Label the system with the new refrigerant and oil so the next tech doesn't mix refrigerants.
Retrofit, recharge or replace?
- Recharge with R-22 when the leak is repaired and reclaimed R-22 is available (R-22 guide).
- Retrofit when the equipment is sound but R-22 is impractical.
- Replace when the equipment is near the end of its life. New systems must meet the 700 GWP limit, so they use refrigerants such as R-454B or R-32.
On the EPA 608 exam
Substitute refrigerants, oils and the 'no drop-in' rule are Core exam topics.
Test yourself: 6 Core questions on substitutes and oils
Substitutes and oils are on the Core exam
Test yourself free on the section every EPA 608 certification requires.
Frequently asked questions
Is R-407C a replacement for R-22?
Yes. EPA SNAP lists R-407C as acceptable for retrofitting R-22 residential and light-commercial AC systems. Like every substitute it is not a true drop-in; follow the refrigerant maker's retrofit procedure, including oil.
What year did R-22 switch to R-410A?
New equipment switched in 2010, when R-22 production for use in new equipment ended. R-22 production and import ended completely on January 1, 2020.
Can I replace my R-22 with R-410A?
Not in the same system. R-410A is not listed for R-22 retrofits and runs at much higher pressure; switching to R-410A means new equipment designed for it.
Is there a drop-in replacement for R-22?
No true drop-in exists. EPA's test topics stress that there are no drop-in replacements: changing refrigerant means a retrofit with compatible oil and components.
Sources
- EPA SNAP — Substitutes in Residential and Light Commercial AC and Heat Pumps (updated March 19, 2026)
- EPA — Technology Transitions GWP Reference Table (updated April 2, 2026)
- EPA — Technology Transitions HFC Restrictions by Sector (updated August 28, 2026)
- EPA — Section 608 Test Topics (updated November 24, 2026)
- EPA — Phaseout of Class II Ozone-Depleting Substances (updated April 1, 2026)