Quick answer: Evacuation means pulling a vacuum on a system. It serves two purposes: removing refrigerant to EPA's required levels before opening or disposing of an appliance, and dehydrating the system (removing air and moisture) before charging. Measure deep vacuum with a micron gauge, not a compound gauge, and never run a hermetic compressor under vacuum.
By the TradeCert Prep editorial team · Last reviewed: November 26, 2026 · How we research and check our content
Required evacuation levels (40 CFR 82.156)
| Appliance type | Recovery equipment made before Nov. 15, 1993 | Made on or after Nov. 15, 1993 |
|---|---|---|
| Very high-pressure appliance (e.g. R-13, R-23, R-503) | 0 | 0 |
| High-pressure appliance (e.g. R-22, R-410A, R-407C, R-502), or isolated component, full charge less than 200 lb | 0 | 0 |
| High-pressure appliance, or isolated component, full charge 200 lb or more | 4 | 10 |
| Medium-pressure appliance (e.g. R-12, R-134a, R-500, R-114, R-124), or isolated component, full charge less than 200 lb | 4 | 10 |
| Medium-pressure appliance, or isolated component, full charge 200 lb or more | 4 | 15 |
| Low-pressure appliance (e.g. R-11, R-123, R-113, R-245fa) | 25 mm Hg absolute | 25 mm Hg absolute (about 29 in Hg vacuum) |
Source: 40 CFR 82.156(a), Table 1. Small appliances follow separate recovery-percentage rules; see refrigerant recovery.
Inches of mercury vs microns
Gauges show vacuum in inches of mercury (in Hg) below atmosphere; micron gauges show absolute pressure in microns of mercury. One inch of mercury is 25,400 microns, and standard atmosphere is about 29.92 in Hg (about 760,000 microns).
| Vacuum (in Hg) | Absolute pressure (microns) |
|---|---|
| 0 | 759,968 |
| 10 | 505,968 |
| 15 | 378,968 |
| 25 | 124,968 |
| 29 | 23,368 |
That's why a compound gauge can't confirm dehydration: the last inch of mercury spans about 25,000 microns. Use a micron (electronic vacuum) gauge.
How to evacuate and dehydrate a system
- Recover the refrigerant first. A vacuum pump is never a recovery device.
- Leak-test with dry nitrogen and fix any leaks (leak detection).
- Connect the vacuum pump with short, large-diameter hoses and remove valve cores if the manufacturer allows; put the micron gauge at the system, not at the pump.
- Pull to the manufacturer's target. For wet systems, triple evacuate: pull a vacuum, break it with dry nitrogen, and repeat.
- Isolate the pump and do a decay test: watch whether the micron reading holds, levels off (moisture) or keeps climbing (leak).
- Never energize a hermetic compressor while the system is under vacuum (EPA test topics).
- For chillers, circulate or drain the water during evacuation to prevent freezing.
On the EPA 608 exam
Evacuation levels by appliance type and date are classic Type II and Type III questions.
Test yourself: 6 Type II evacuation questions
Memorize the evacuation table
Evacuation levels are some of the most-tested numbers in Type II. Practice them free.
Frequently asked questions
What is the purpose of evacuation and dehydration?
To remove air and moisture before charging. Moisture reacts with refrigerant and oil to form acids and can freeze at the metering device; air (a non-condensable) raises head pressure. EPA's test topics state the system must be evacuated to eliminate air and moisture at the end of service.
What evacuation level is required before opening or disposing of a system?
It depends on the appliance type, charge size and the recovery equipment's date: from 0 in Hg for high-pressure appliances under 200 lb up to 25 mm Hg absolute for low-pressure appliances. The full table from 40 CFR 82.156 is on this page.
What is triple evacuation?
Pulling a vacuum, breaking it with dry nitrogen, and repeating, usually three times, so the nitrogen sweeps out moisture and air between pulls before the final deep vacuum.
How do I know the system is dry?
Isolate the vacuum pump and watch a micron gauge. A reading that rises then levels off suggests remaining moisture; one that keeps rising toward atmosphere suggests a leak. Follow the equipment maker's target micron level.