This lesson covers the rules for small appliances: what counts as a small appliance, required recovery levels, and who is responsible when an appliance is disposed of.
Key numbers
- Under Section 608, a 'small appliance' is one that is fully manufactured, charged and hermetically sealed in a
- 5 pounds or less of refrigerant
- Source
Key concepts
What counts as a small appliance
Household refrigerators and freezers are listed small appliances. Car AC systems are MVACs (Section 609), and rooftop units and chillers are not small appliances.
Source: 40 CFR 82.152 – Definitions.
Room AC and PTAC units
The definition lists room air conditioners including window units, portable units and packaged terminal air heat pumps, plus dehumidifiers, under-counter ice makers, vending machines and water coolers.
Source: 40 CFR 82.152 – Definitions.
Drinking water coolers
Drinking water coolers are explicitly listed in the definition of small appliance, as long as they are factory-sealed with 5 lb or less.
Source: 40 CFR 82.152 – Definitions.
What to know
- Using recovery equipment manufactured AFTER November 15, 1993, on a small appliance with an OPERATING compressor, you must recover 90% of the refrigerant. With post-11/15/1993 equipment and a working compressor, the requirement is 90% recovery (or evacuation to 4 inches of mercury vacuum).
- When the compressor is not functioning, the requirement is 80% recovery (or 4 inches of mercury vacuum).
- Using recovery equipment manufactured BEFORE November 15, 1993, on a small appliance, you must recover 80% of the refrigerant regardless of compressor condition. With pre-11/15/1993 recovery equipment, the requirement is 80% recovery whether the compressor works or not (or evacuation to 4 inches Hg vacuum).
- 40 CFR 82.156(b)(3) lets technicians satisfy the small-appliance requirement by evacuating to four inches of mercury vacuum.
- 40 CFR 82.158 requires small-appliance recovery equipment to be certified as capable of recovering 90% with the test-stand compressor operating and 80% when it is not operating.
- The final person in the disposal chain, such as the scrap recycler or landfill, is responsible for making sure refrigerant is removed from a small appliance. Under the safe disposal rule they must either recover the remaining refrigerant or verify, with a signed statement, that it was recovered earlier.
- The signed statement must include the name and address of the person who recovered the refrigerant and the date it was recovered.
- The final processor must keep copies of signed statements or contracts for disposed small appliances on site for three years (40 CFR 82.155(c)).
- EPA says people recovering refrigerant from small appliances for disposal don't have to be certified, but the recovery equipment must meet the same performance standards and venting is still prohibited.
- EPA does not mandate or accept a sticker as verification. The final disposer needs a signed statement or a qualifying contract.
- Appendix D lets organizations offering Type I choose an on-site format or a mail-in format. Type II, III and Universal must be closed-book and proctored.
- Appendix D: the passing score for closed-book tests is 70%, while mail-in format Type I tests require 84%.
Source: EPA – Stationary Refrigeration Service Practice Requirements, 40 CFR 82.156 – Proper evacuation of refrigerant, 40 CFR 82.158 – Standards for recovery and/or recycling equipment, EPA – Stationary Refrigeration Safe Disposal Requirements, 40 CFR 82.155 – Safe disposal of appliances, 40 CFR Part 82 Subpart F, Appendix D – Standards for certifying programs.
Scenario
A technician uses a recovery machine built in 2012 on a dehumidifier with a working compressor. With post-1993 equipment and a working compressor, the minimum is 90% of the refrigerant, or the alternative of evacuating to 4 inches Hg vacuum.