Leak detection (EPA 608 Type III)

4 min read · Lesson 1 of 6 in Type III

This lesson covers finding leaks in low-pressure systems, where air leaks in instead of refrigerant leaking out, and how leak testing is done safely.

Key numbers

Leak-test pressure limit
No more than 10 psig
Source
Rupture disc
Relieves at 15 psig
Source
If nitrogen is used to leak test a low-pressure centrifugal chiller, the maximum test pressure is
10 psig
Source
Why is leak-test pressure on a low-pressure chiller limited
To protect the rupture disc, which is typically set at 15 psig
Source

Key concepts

Leaks pull air in

Parts of a low-pressure system run in a vacuum, so leaks pull air and moisture in rather than pushing refrigerant out.

Source: EPA – Section 608 Test Topics.

Excessive purging

EPA's Type III topics list excessive purging as a sign of leakage. The purge unit has to keep removing air that is leaking in.

Source: EPA – Section 608 Test Topics.

Pressurizing for a leak test

EPA's order of preference for low-pressure systems: hot water method or a built-in heating/pressurization device such as Prevac first, then nitrogen.

Source: EPA – Section 608 Test Topics.

What to know

  • Low-pressure chillers have a rupture disc on the evaporator, typically 15 psig, to protect the shell from over-pressurization.
  • A hydrostatic tube test, or testing the water circuit for refrigerant, helps determine whether a tube leak lets refrigerant and water mix.
  • Frequent purging means non-condensables are entering, which usually indicates a leak somewhere in the vacuum side of the system.
  • 40 CFR 82.157(g)(2): leak inspections must be done by a certified technician.
  • Before leak testing a low-pressure chiller with nitrogen, you should first raise the pressure with heat (hot water or Prevac) as far as possible. EPA prefers heat-based pressurization; nitrogen is used after that, with care not to exceed 10 psig.
  • After using nitrogen to pressurize a low-pressure chiller for a leak test, the nitrogen must be removed, which usually requires purging, so its use is limited. Nitrogen is a non-condensable and must later be removed by purging/evacuation, which can release some refrigerant. That's why heat-based methods are preferred.
  • Moisture can enter from a leaking tube (water side) or with air drawn in through leaks on the vacuum side.

Source: EPA – Section 608 Test Topics, 40 CFR 82.157 – Appliance maintenance and leak repair, EPA – Stationary Refrigeration Service Practice Requirements.

Scenario

A low-pressure chiller needs a leak test. Following EPA's order of preference, the tech raises pressure with controlled hot water or a built-in heating/pressurization device (Prevac) first and checks with a leak detector; nitrogen comes after that.

Source: EPA – Section 608 Test Topics.

Check what you remember

1. Low-pressure chillers (e.g., R-123) operate with the evaporator below atmospheric pressure. Because of this, leaks usually cause:

Choices
Check answer

Correct answer: B. Air and moisture to leak INTO the system

Parts of a low-pressure system run in a vacuum, so leaks pull air and moisture in rather than pushing refrigerant out.

Source: EPA – Section 608 Test Topics

2. A sign of leakage into a low-pressure system is:

Choices
Check answer

Correct answer: B. Excessive purging (the purge unit running often)

EPA's Type III topics list excessive purging as a sign of leakage. The purge unit has to keep removing air that is leaking in.

Source: EPA – Section 608 Test Topics

3. What is EPA's preferred first method for pressurizing a low-pressure system for a leak test?

Choices
Check answer

Correct answer: D. Controlled hot water or a built-in system heating/pressurization device such as Prevac

EPA's order of preference for low-pressure systems: hot water method or a built-in heating/pressurization device such as Prevac first, then nitrogen.

Source: EPA – Section 608 Test Topics

4. If nitrogen is used to leak test a low-pressure centrifugal chiller, the maximum test pressure is:

Choices
Check answer

Correct answer: D. 10 psig

Do not exceed 10 psig when leak testing a low-pressure chiller. The evaporator rupture disc is typically set at 15 psig.

Source: EPA – Section 608 Test Topics