  1. Large high-pressure refrigerant leaks in a mechanical room are dangerous mainly because:

    1. They cause the lights to flicker
    2. They lower the room humidity
    3. The refrigerant is lighter than air
    4. The refrigerant can displace oxygen and cause suffocation
  2. An industrial ice machine or an ice rink system is classified as:

    1. Small appliance
    2. Comfort cooling
    3. Industrial process refrigeration
    4. Commercial refrigeration
  3. System-dependent recovery equipment is prohibited on appliances containing more than:

    1. 50 lb
    2. 15 lb
    3. 5 lb
    4. 100 lb
  4. Traces of oil on fittings or around the compressor of a hermetic system usually indicate:

    1. Normal operation
    2. Overcharging
    3. A clogged filter
    4. A refrigerant leak at that location
  5. Using the PT chart, R-410A at a saturation temperature of 40°F is about 118 psig. If the suction line temperature is 50°F at 118 psig, the superheat is:

    1. 0°F
    2. 118°F
    3. 10°F
    4. 40°F
  6. A rooftop unit holds 18 lb of R-410A. Using a modern recovery machine, the required recovery level is:

    1. 0 inches Hg
    2. 10 inches Hg vacuum
    3. 15 inches Hg vacuum
    4. 4 inches Hg vacuum
  7. When transferring liquid refrigerant into a recovery cylinder, how can you tell when the cylinder reaches 80% full?

    1. By touching it
    2. By the cylinder color
    3. By weighing the cylinder on a scale or using a float/level switch
    4. By the sound
  8. What is the leak-rate trigger for comfort cooling appliances?

    1. 20%
    2. 10%
    3. 30%
    4. 15%
  9. The push-pull method generally should not be used when:

    1. The system holds a large, accessible liquid charge
    2. The system holds only a small charge, or the liquid can't be isolated (e.g., some heat pumps with reversing valves)
    3. The system uses R-22
    4. The system has a receiver
  10. If a tracer gas is needed so an electronic detector can sense a leak, what is acceptable according to EPA test topics?

    1. Compressed air
    2. Oxygen with R-22
    3. Pure R-22 at high pressure
    4. Nitrogen with a trace quantity of HCFC-22
  11. Why should you not open the system or add refrigerant before identifying the refrigerant in it?

    1. DOT requires it
    2. Mixing refrigerants causes unpredictable pressures and can make recovered refrigerant unreclaimable
    3. The color might be wrong
    4. It voids the thermostat
  12. Before changing the oil in a high-pressure appliance, the appliance (or isolated part) must be evacuated to no higher than:

    1. 5 psig
    2. 10 psig
    3. 15 psig
    4. 0 psig
  13. Before leak testing with nitrogen, the nitrogen cylinder must be fitted with:

    1. A sight glass
    2. Nothing; tank pressure is fine
    3. A pressure regulator, and a relief valve in the line
    4. A Schrader core
  14. For a commercial refrigeration appliance with 500 or more pounds that exceeded its trigger rate, leak inspections must be done:

    1. Monthly forever
    2. Quarterly, until it shows no excess leaks for four quarters in a row
    3. Never
    4. Once a year
  15. Which practice speeds up recovery?

    1. Heating the recovery cylinder
    2. Using longer, smaller hoses
    3. Chilling the recovery vessel or heating the appliance
    4. Recovering through a Schrader core
  16. Why should a system be leak tested before it is charged?

    1. To raise superheat
    2. To test the thermostat
    3. Because EPA requires dye in all systems
    4. So that refrigerant isn't lost through leaks after charging
  17. An R-22 system has a condensing (saturation) temperature of 120°F and a liquid line temperature of 110°F. The subcooling is:

    1. 10°F
    2. 230°F
    3. 110°F
    4. 0°F
  18. When evacuating a system for disposal, the required evacuation levels are:

    1. Always 500 microns
    2. The same as the Table 1 levels used for service
    3. Not required
    4. Always 0 psig
  19. ASHRAE Standard 15 requires which device in equipment rooms for all refrigerants?

    1. A smoke detector
    2. An oxygen deprivation sensor/refrigerant monitor
    3. A carbon monoxide detector only
    4. A sprinkler head
  20. The leak rate is calculated each time refrigerant is:

    1. Added to the appliance
    2. Reclaimed
    3. Recovered
    4. Sold
  21. To speed up recovery from a large high-pressure system, you should begin by recovering:

    1. Oil first
    2. Nitrogen first
    3. Liquid first
    4. Vapor first
  22. Before charging or recharging equipment, a technician should:

    1. Replace the compressor
    2. Leak test the system
    3. Add oil
    4. Vent the lines
  23. Which refrigerants are listed by EPA as examples used in high-pressure appliances?

    1. R-22, R-407C and R-410A
    2. R-12 and R-500
    3. R-23 and R-503
    4. R-11 and R-123
  24. Using recovery equipment manufactured BEFORE Nov 15, 1993, a high-pressure appliance with less than 200 lb must be evacuated to:

    1. 15 inches Hg vacuum
    2. 10 inches Hg vacuum
    3. 4 inches Hg vacuum
    4. 0 inches Hg
  25. When leak testing with nitrogen, the system should never be pressurized above:

    1. 500 psig always
    2. The cylinder pressure
    3. Atmospheric pressure
    4. The pressure shown on the nameplate (or manufacturer's maximum test pressure)
  1. D. The refrigerant can displace oxygen and cause suffocation (Type II safety)

    Refrigerant vapor is heavier than air and can displace oxygen, which is why ASHRAE 15 requires sensors and alarms.

    Source: EPA – Section 608 Test Topics

  2. C. Industrial process refrigeration (Leak repair requirements)

    EPA includes industrial ice machines, appliances used directly in generating electricity, and ice rinks in industrial process refrigeration.

    Source: EPA – Stationary Refrigeration Leak Repair Requirements

  3. B. 15 lb (Recovery techniques)

    40 CFR 82.156(e): system-dependent equipment may not be used on appliances with a full charge of more than 15 pounds of refrigerant unless it is permanently attached to the appliance as a pump-out unit.

    Source: 40 CFR 82.156 – Proper evacuation of refrigerant

  4. D. A refrigerant leak at that location (Leak detection)

    Oil travels with refrigerant, so oil traces at joints and fittings are a classic sign of a leak, as listed in EPA's Type II topics.

    Source: EPA – Section 608 Test Topics

  5. C. 10°F (Refrigeration & components)

    Superheat = actual vapor line temperature − saturation temperature = 50°F − 40°F = 10°F.

    Source: EPA – Section 608 Test Topics

  6. A. 0 inches Hg (Evacuation requirements)

    R-410A is a high-pressure refrigerant; under 200 lb = 0 inches Hg (0 psig).

    Source: EPA – Stationary Refrigeration Service Practice Requirements

  7. C. By weighing the cylinder on a scale or using a float/level switch (Type II safety)

    Weigh the cylinder (or use a float switch) to stay within 80% of capacity, using the cylinder's tare weight and water capacity.

    Source: EPA – Section 608 Test Topics

  8. B. 10% (Leak repair requirements)

    Comfort cooling has a 10% trigger leak rate. Under 40 CFR 82.157 this applies to appliances with 50 lb or more of an ozone-depleting refrigerant; since January 1, 2026, 40 CFR 84.106 applies the same 10% rate to comfort cooling appliances with 15 lb or more of an HFC or other substitute with GWP above 53 (residential and light commercial AC and heat pumps are excluded).

    Source: EPA – Stationary Refrigeration Leak Repair Requirements

  9. B. The system holds only a small charge, or the liquid can't be isolated (e.g., some heat pumps with reversing valves) (Recovery techniques)

    Push-pull works best on systems with a large charge of liquid that you can isolate (for example at a receiver). It's not practical for small charges or for systems where liquid can't be isolated, such as some heat pumps, where you recover vapor instead.

    Source: EPA – Section 608 Test Topics

  10. D. Nitrogen with a trace quantity of HCFC-22 (Leak detection)

    EPA's Type II topics rank leak-test gases: nitrogen alone is best, and nitrogen with only a trace of HCFC-22 (so an electronic detector can sense it) is better than pressurizing with pure refrigerant.

    Source: EPA – Section 608 Test Topics

  11. B. Mixing refrigerants causes unpredictable pressures and can make recovered refrigerant unreclaimable (Refrigeration & components)

    Mixed refrigerants have unpredictable PT behavior and may be impossible to reclaim. Always identify the refrigerant first.

    Source: EPA – Section 608 Test Topics

  12. A. 5 psig (Evacuation requirements)

    EPA: it is a violation to change oil at higher than 5 psig. Evacuate to no more than 5 psig, or drain the oil into a receiver that is then evacuated to 5 psig or lower.

    Source: EPA – Stationary Refrigeration Service Practice Requirements

  13. C. A pressure regulator, and a relief valve in the line (Type II safety)

    A full nitrogen cylinder can hold over 2,000 psig. Always use a regulator and a relief valve to avoid over-pressurizing the system.

    Source: EPA – Section 608 Test Topics

  14. B. Quarterly, until it shows no excess leaks for four quarters in a row (Leak repair requirements)

    82.157(g): commercial and industrial process refrigeration with a full charge of 500+ pounds must be inspected quarterly until four consecutive quarters show no leaks above the trigger rate.

    Source: 40 CFR 82.157 – Appliance maintenance and leak repair

  15. C. Chilling the recovery vessel or heating the appliance (Recovery techniques)

    EPA lists chilling the recovery vessel and heating the appliance or vessel being recovered from as ways to speed recovery. Removing Schrader cores and using short, wide hoses also helps.

    Source: EPA – Section 608 Test Topics

  16. D. So that refrigerant isn't lost through leaks after charging (Leak detection)

    Charging a leaking system wastes refrigerant and releases it to the environment, so leak test before charging.

    Source: EPA – Section 608 Test Topics

  17. A. 10°F (Refrigeration & components)

    Subcooling = saturation (condensing) temperature − actual liquid line temperature = 120°F − 110°F = 10°F.

    Source: EPA – Section 608 Test Topics

  18. B. The same as the Table 1 levels used for service (Evacuation requirements)

    40 CFR 82.156 applies the same Table 1 evacuation levels when opening an appliance for maintenance, service, repair or disposal.

    Source: 40 CFR 82.156 – Proper evacuation of refrigerant

  19. B. An oxygen deprivation sensor/refrigerant monitor (Type II safety)

    EPA's topics: equipment rooms under ASHRAE 15 need an oxygen deprivation sensor with all refrigerants (and refrigerant monitors that trigger alarms and ventilation).

    Source: EPA – Section 608 Test Topics

  20. A. Added to the appliance (Leak repair requirements)

    40 CFR 82.157(b): owners or operators must calculate the leak rate every time refrigerant is added to an appliance, unless the addition is made immediately after a retrofit or the installation of a new appliance, or qualifies as a seasonal variance.

    Source: 40 CFR 82.157 – Appliance maintenance and leak repair

  21. C. Liquid first (Recovery techniques)

    EPA's Type II topics: recovering liquid at the beginning speeds up the process, since liquid holds far more refrigerant per volume than vapor.

    Source: EPA – Section 608 Test Topics

  22. B. Leak test the system (Leak detection)

    EPA's Type II topics include the need to leak test before charging or recharging equipment.

    Source: EPA – Section 608 Test Topics

  23. A. R-22, R-407C and R-410A (Refrigeration & components)

    40 CFR 82.152 lists R-22, R-407A, R-407C, R-410A and R-502 as examples of high-pressure refrigerants.

    Source: 40 CFR 82.152 – Definitions

  24. D. 0 inches Hg (Evacuation requirements)

    EPA's table: high-pressure appliances under 200 lb = 0 inches Hg with both pre- and post-1993 equipment.

    Source: EPA – Stationary Refrigeration Service Practice Requirements

  25. D. The pressure shown on the nameplate (or manufacturer's maximum test pressure) (Type II safety)

    Use a regulator and relief valve and never exceed the equipment's rated test pressure on the nameplate or from the manufacturer.

    Source: EPA – Section 608 Test Topics