Evacuation requirements: Type II practice

16 published questions in this topic. Free Evacuation requirements practice for EPA 608 Type II, with instant feedback, explanations and source links.

10 published questionsFeedback appears after each answer
Type II · Evacuation requirementsQuestion 1 of 10

A system holds 250 lb of R-22 and the technician's recovery machine was built in 2015. The required recovery level is:

Answer choices for question 1

Keyboard: A–D to choose · Enter to check

Type II · Evacuation requirementsQuestion 2 of 10

A very high-pressure appliance (e.g., R-23) must be evacuated to:

Answer choices for question 2

Keyboard: A–D to choose · Enter to check

Type II · Evacuation requirementsQuestion 3 of 10

A rooftop unit holds 18 lb of R-410A. Using a modern recovery machine, the required recovery level is:

Answer choices for question 3

Keyboard: A–D to choose · Enter to check

Type II · Evacuation requirementsQuestion 4 of 10

Before changing the oil in a high-pressure appliance, the appliance (or isolated part) must be evacuated to no higher than:

Answer choices for question 4

Keyboard: A–D to choose · Enter to check

Type II · Evacuation requirementsQuestion 5 of 10

Using post-1993 recovery equipment, a medium-pressure appliance with 200 lb OR MORE must be evacuated to:

Answer choices for question 5

Keyboard: A–D to choose · Enter to check

Type II · Evacuation requirementsQuestion 6 of 10

Using recovery equipment manufactured after Nov 15, 1993, a high-pressure appliance with 200 lb OR MORE of refrigerant must be evacuated to:

Answer choices for question 6

Keyboard: A–D to choose · Enter to check

Type II · Evacuation requirementsQuestion 7 of 10

Using recovery equipment manufactured after Nov 15, 1993, a high-pressure appliance with LESS than 200 lb of refrigerant must be evacuated to:

Answer choices for question 7

Keyboard: A–D to choose · Enter to check

Type II · Evacuation requirementsQuestion 8 of 10

Using post-1993 recovery equipment, a medium-pressure appliance (e.g., R-134a) with LESS than 200 lb must be evacuated to:

Answer choices for question 8

Keyboard: A–D to choose · Enter to check

Type II · Evacuation requirementsQuestion 9 of 10

When evacuating a system for disposal, the required evacuation levels are:

Answer choices for question 9

Keyboard: A–D to choose · Enter to check

Type II · Evacuation requirementsQuestion 10 of 10

Required evacuation levels in inches of mercury vacuum are measured relative to:

Answer choices for question 10

Keyboard: A–D to choose · Enter to check

Ready for a full-length run?

Take a free timed mock for Type II or the full Universal: real section length and pass mark, instant score, no signup.

About this topic

Evacuation requirements for covered appliances. This page draws 10 questions from the 16 sourced Type II questions we have on evacuation requirements; each answer explains why and links to the rule it tests.

On the real test: Every Type II section on the real exam has 25 questions drawn across all Type II topics, and you need 18 of 25 (70%) on the closed-book test. Our bank has 16 practice questions on this topic. Expect questions like: “Using recovery equipment manufactured BEFORE Nov 15, 1993, a high-pressure appliance with less than 200 lb must be evacuated to:” and “A very high-pressure appliance (e.g., R-23) must be evacuated to:”

Key facts to remember

  • High-pressure, under 200 lb (post-1993 equipment) 0 in Hg vacuum (source)
  • High-pressure, 200 lb or more (post-1993) 10 in Hg vacuum (source)
  • Medium-pressure, under 200 lb (post-1993) 10 in Hg vacuum (source)
  • Medium-pressure, 200 lb or more (post-1993) 15 in Hg vacuum (source)