  1. Before draining oil from a low-pressure system, the oil should be heated to about:

    1. 70°F
    2. 200°F
    3. 130°F
    4. 32°F
  2. Why does R-123 need careful handling compared with R-22 or R-410A?

    1. It is radioactive
    2. It is in ASHRAE safety group B1 (higher toxicity), so exposure limits are lower
    3. It is a very high-pressure gas
    4. It is flammable
  3. Under ASHRAE Standard 15, an equipment room with an R-123 chiller requires:

    1. Only a smoke detector
    2. No special equipment
    3. An open window
    4. A refrigerant sensor/monitor (in addition to oxygen deprivation protection)
  4. Which methods may be used to pressurize an R-123 chiller to 0 psig for a non-major repair?

    1. Compressed air
    2. Controlled hot water or a system heating/pressurization device such as Prevac
    3. Oxygen
    4. Nitrogen only
  5. After an owner creates a retrofit or retirement plan for a leaking appliance, EPA can relieve the owner of the obligation to retrofit or retire if:

    1. Within 180 days of the plan's date the owner shows the appliance no longer exceeds the leak rate and agrees in writing to repair all identified leaks within one year
    2. The owner waits a year
    3. The owner vents the remaining refrigerant
    4. The owner switches the appliance to R-22
  6. After using nitrogen to pressurize a low-pressure chiller for a leak test, the nitrogen:

    1. Stays in the system permanently
    2. Must be removed, which usually requires purging, so its use is limited
    3. Becomes refrigerant
    4. Is absorbed by the oil
  7. Vapor is charged into an evacuated R-123 chiller until the saturation temperature reaches about 32°F, which corresponds to roughly:

    1. 10 psig
    2. 0 psig
    3. 29.9 inches Hg vacuum
    4. 20 inches Hg vacuum
  8. The low-pressure chiller component that holds the boiling refrigerant and cools the chilled water is the:

    1. Evaporator (cooler)
    2. Condenser
    3. Economizer only
    4. Purge unit
  9. Why should a technician avoid using open flames near a refrigerant leak in a chiller room?

    1. It triggers the purge unit
    2. Refrigerant can decompose into toxic gases such as phosgene and acids
    3. It makes the room too warm
    4. It damages paint
  10. The 25 mm Hg absolute requirement for low-pressure appliances applies when:

    1. Only for disposal
    2. Only for appliances under 200 lb
    3. Only for R-113
    4. Opening the appliance for maintenance, service, repair or disposal (unless an exception applies)
  11. Purged refrigerant destroyed at a verified destruction efficiency of at least ___ may be excluded from leak-rate calculations.

    1. 90%
    2. 75%
    3. 50%
    4. 98%
  12. If nitrogen is used to leak test a low-pressure centrifugal chiller, the maximum test pressure is:

    1. 15 psig
    2. 50 psig
    3. 5 psig
    4. 10 psig
  13. Heating the oil to 130°F before draining it from a low-pressure chiller helps because:

    1. It kills bacteria
    2. Warm oil holds less dissolved refrigerant, so the refrigerant boils out before the oil is drained
    3. It thins the oil for faster draining only
    4. It's required to measure acid
  14. Moisture and air entering a low-pressure system can cause:

    1. Nothing
    2. Acid formation, higher condensing pressure and reduced efficiency
    3. Lower condensing pressure
    4. Better oil return
  15. If a low-pressure chiller is pressurized above the rupture disc setting, what happens?

    1. The water freezes
    2. Nothing
    3. The rupture disc can burst and release the refrigerant charge
    4. The purge unit shuts off
  16. Low-pressure appliances must be evacuated to what level using recovery equipment made after Nov 15, 1993?

    1. 0 psig
    2. 25 mm Hg absolute
    3. 500 microns
    4. 10 inches Hg vacuum
  17. A retrofit or retirement plan for a leaking appliance must be kept:

    1. Nowhere
    2. Only at EPA
    3. By the refrigerant wholesaler
    4. Accessible at the appliance site (paper or electronic) and available to EPA on request
  18. To check whether water tubes in a chiller are leaking, a technician can:

    1. Use a hydrostatic tube test or check the water for refrigerant
    2. Heat the tubes with a torch
    3. Measure the voltage
    4. Pressurize the water box with oxygen
  19. After reaching the required recovery vacuum on a low-pressure system, you should wait a few minutes because:

    1. EPA requires a 1-hour wait
    2. A pressure rise indicates liquid refrigerant remaining in the system or oil
    3. It improves the oil
    4. The machine must cool down
  20. Which low-GWP refrigerant does EPA list (A1) as a substitute in centrifugal chillers, including low-pressure machines?

    1. R-290
    2. R-454B
    3. R-32
    4. R-1233zd(E)
  21. In a large R-123 leak in a mechanical room, technicians should:

    1. Enter immediately without protection
    2. Evacuate the area and use a self-contained breathing apparatus (SCBA) if entry is necessary
    3. Use a torch to burn off the refrigerant
    4. Turn off the ventilation
  22. If leaks make it impossible to reach 25 mm Hg absolute, the technician must evacuate leaking components to the lowest level achievable without substantially contaminating the refrigerant, but not higher than:

    1. 10 psig
    2. 0 psig
    3. 15 inches Hg
    4. 25 mm Hg
  23. A low-pressure chiller used to cool an industrial process (e.g., a chemical plant) with 50+ lb falls under which trigger rate?

    1. 20%
    2. 35%
    3. 30%
    4. 10%
  24. A low-pressure chiller's purge unit runs much more than normal. The technician should first suspect:

    1. A dirty condenser coil on a rooftop unit
    2. Too much refrigerant
    3. A broken thermostat
    4. An air leak into the system
  25. Recovered refrigerant from a low-pressure chiller that will be put back into the same owner's chiller:

    1. Must be reclaimed first
    2. Can be returned without reclamation
    3. Must be destroyed
    4. Must be sold to a wholesaler
  1. C. 130°F (Recovery & recharging techniques)

    EPA's Type III topics: heat the oil to 130°F before removing it, to drive out dissolved refrigerant and minimize release.

    Source: EPA – Section 608 Test Topics

  2. B. It is in ASHRAE safety group B1 (higher toxicity), so exposure limits are lower (Purge units & refrigeration)

    R-123 is ASHRAE B1: higher toxicity (B) and no flame propagation (1). That is why ASHRAE 15 requires a refrigerant sensor in R-123 equipment rooms.

    Source: EPA – Section 608 Test Topics

  3. D. A refrigerant sensor/monitor (in addition to oxygen deprivation protection) (Type III safety)

    EPA's Type III topics: under ASHRAE 15, an equipment room refrigerant sensor is needed for R-123, and oxygen deprivation sensors are needed for all refrigerants.

    Source: EPA – Section 608 Test Topics

  4. B. Controlled hot water or a system heating/pressurization device such as Prevac (Evacuation requirements)

    EPA's topics list controlled hot water and system heating devices such as Prevac. For refrigerants with boiling points at or below 85°F, like R-11 and R-123, methods requiring later purging (nitrogen) may not be used.

    Source: 40 CFR 82.156 – Proper evacuation of refrigerant

  5. A. Within 180 days of the plan's date the owner shows the appliance no longer exceeds the leak rate and agrees in writing to repair all identified leaks within one year (Leak repair requirements)

    40 CFR 82.157(h)(5)(ii): the owner may ask EPA for relief if, within 180 days of the plan's date, it shows the appliance no longer exceeds the applicable leak rate and agrees in writing to repair all identified leaks within one year of the plan's date.

    Source: 40 CFR 82.157 – Appliance maintenance and leak repair

  6. B. Must be removed, which usually requires purging, so its use is limited (Leak detection)

    Nitrogen is a non-condensable and must later be removed by purging/evacuation, which can release some refrigerant. That's why heat-based methods are preferred.

    Source: EPA – Stationary Refrigeration Service Practice Requirements

  7. D. 20 inches Hg vacuum (Recovery & recharging techniques)

    R-123 saturates at 32°F at about 4.7 psia, roughly 20 inches Hg vacuum (computed with CoolProp). Above that point you can switch to liquid charging without freezing tube water.

    Source: EPA – Section 608 Test Topics

  8. A. Evaporator (cooler) (Purge units & refrigeration)

    In a chiller, refrigerant boils in the evaporator (cooler) shell, absorbing heat from the chilled water in the tubes.

    Source: EPA – Section 608 Test Topics

  9. B. Refrigerant can decompose into toxic gases such as phosgene and acids (Type III safety)

    Fluorocarbon refrigerants decompose at high temperatures into toxic and corrosive products.

    Source: EPA – Section 608 Test Topics

  10. D. Opening the appliance for maintenance, service, repair or disposal (unless an exception applies) (Evacuation requirements)

    Table 1 evacuation levels apply when opening appliances for maintenance, service, repair or disposal, with limited exceptions for leaks and non-major repairs.

    Source: 40 CFR 82.156 – Proper evacuation of refrigerant

  11. D. 98% (Leak repair requirements)

    82.157(k): purged refrigerant destroyed at 98% or greater verifiable efficiency is not counted toward the leak rate.

    Source: 40 CFR 82.157 – Appliance maintenance and leak repair

  12. D. 10 psig (Leak detection)

    Do not exceed 10 psig when leak testing a low-pressure chiller. The evaporator rupture disc is typically set at 15 psig.

    Source: EPA – Section 608 Test Topics

  13. B. Warm oil holds less dissolved refrigerant, so the refrigerant boils out before the oil is drained (Recovery & recharging techniques)

    Warm oil releases dissolved refrigerant, so less refrigerant leaves with the drained oil.

    Source: EPA – Section 608 Test Topics

  14. B. Acid formation, higher condensing pressure and reduced efficiency (Purge units & refrigeration)

    Non-condensables raise head pressure, and moisture reacts with refrigerant and oil to form acids, so the purge unit's job is important.

    Source: EPA – Section 608 Test Topics

  15. C. The rupture disc can burst and release the refrigerant charge (Type III safety)

    Over-pressurizing past the rupture disc rating (typically 15 psig) can burst it and release refrigerant, which is why leak tests are limited to 10 psig.

    Source: EPA – Section 608 Test Topics

  16. B. 25 mm Hg absolute (Evacuation requirements)

    EPA's table: low-pressure appliances = 25 mm Hg absolute with either pre- or post-1993 equipment.

    Source: EPA – Stationary Refrigeration Service Practice Requirements

  17. D. Accessible at the appliance site (paper or electronic) and available to EPA on request (Leak repair requirements)

    40 CFR 82.157(h)(3): the plan must be signed by an authorized company official, dated, accessible at the site of the appliance in paper or electronic format, and available for EPA inspection upon request.

    Source: 40 CFR 82.157 – Appliance maintenance and leak repair

  18. A. Use a hydrostatic tube test or check the water for refrigerant (Leak detection)

    A hydrostatic tube test, or testing the water circuit for refrigerant, helps determine whether a tube leak lets refrigerant and water mix.

    Source: EPA – Section 608 Test Topics

  19. B. A pressure rise indicates liquid refrigerant remaining in the system or oil (Recovery & recharging techniques)

    If pressure rises after reaching the required vacuum, refrigerant is still boiling out of liquid or oil, so continue recovering.

    Source: EPA – Section 608 Test Topics

  20. D. R-1233zd(E) (Purge units & refrigeration)

    EPA's SNAP list for centrifugal chillers includes R-1233zd(E), an A1 low-pressure HCFO refrigerant with a near-zero ODP (about 0.0003) and a GWP under 10, used in new low-pressure chillers as an R-123 alternative.

    Source: EPA SNAP – Substitutes in centrifugal chillers

  21. B. Evacuate the area and use a self-contained breathing apparatus (SCBA) if entry is necessary (Type III safety)

    Large releases can displace oxygen and, for R-123, exceed exposure limits. Leave the area, ventilate, and use SCBA if entry is required.

    Source: EPA – Section 608 Test Topics

  22. B. 0 psig (Evacuation requirements)

    40 CFR 82.156(a)(2)(iii): evacuate leaking components to the lowest attainable level, which may not exceed 0 psig.

    Source: EPA – Stationary Refrigeration Service Practice Requirements

  23. C. 30% (Leak repair requirements)

    Industrial process refrigeration has a 30% trigger leak rate.

    Source: EPA – Stationary Refrigeration Leak Repair Requirements

  24. D. An air leak into the system (Leak detection)

    Frequent purging means non-condensables are entering, which usually indicates a leak somewhere in the vacuum side of the system.

    Source: EPA – Section 608 Test Topics

  25. B. Can be returned without reclamation (Recovery & recharging techniques)

    Recovered refrigerant can go back into the same appliance or other appliances owned by the same person without reclamation.

    Source: EPA – Stationary Refrigeration Service Practice Requirements