Leak detection: Type III practice
13 published questions in this topic. Free Leak detection practice for EPA 608 Type III, with instant feedback, explanations and source links.
Ready for a full-length run?
Take a free timed mock for Type III or the full Universal: real section length and pass mark, instant score, no signup.
About this topic
Leak detection requirements and methods. This page draws 10 questions from the 13 sourced Type III questions we have on leak detection; each answer explains why and links to the rule it tests.
On the real test: Every Type III section on the real exam has 25 questions drawn across all Type III topics, and you need 18 of 25 (70%) on the closed-book test. Our bank has 13 practice questions on this topic. Expect questions like: “If nitrogen is used to leak test a low-pressure centrifugal chiller, the maximum test pressure is:” and “Why is leak-test pressure on a low-pressure chiller limited?”
Key facts to remember
- Leak-test pressure limit No more than 10 psig (source)
- Rupture disc Relieves at 15 psig (source)
- If nitrogen is used to leak test a low-pressure centrifugal chiller, the maximum test pressure is 10 psig (source)
- Why is leak-test pressure on a low-pressure chiller limited To protect the rupture disc, which is typically set at 15 psig (source)
Keep studying
- Learn it in depth: Refrigerant leak detection
- Type III practice test, balanced across every Type III topic
- EPA 608 cheat sheet of the most-tested numbers