How These P-T Charts Are Calculated

Learn how TradeCert Prep calculates pressure-temperature values, blend curves, sea-level psig, interpolation flags, and chart spot checks.

Last reviewed: November 24, 2026

These pressure-temperature values are calculated reference data, not an official EPA or equipment-manufacturer table. CoolProp 8.1.0 uses Helmholtz-energy equations of state through its HEOS backend; blends use nominal ASHRAE 34 mass compositions.

Calculation method

  • For R-410A, the blend is 50/50 R-32/R-125 by mass.
  • For R-404A, the blend is 44/52/4 R-125/R-143a/R-134a by mass.
  • For R-407C, the blend is 23/25/52 R-32/R-125/R-134a by mass.
  • For R-454B, the blend is 68.9/31.1 R-32/R-1234yf by mass.
  • Gauge pressure is calculated as psig = psia − 14.696 at sea level.
  • Bubble pressure is saturated liquid; dew pressure is saturated vapor. The table spans −40°F to 150°F in 5°F steps.

Interpolated values and spot checks

Four values are log-interpolated where the solver did not return a point and are flagged in the CSV: R-410A at 110°F; R-407C at 135°F; and R-454B at 135°F and 145°F.

Spot checks against published manufacturer chart values
Refrigerant and temperatureThis chartPublished chart, approximately
R-410A at 75°F218.7 psig217 psig
R-22 at 40°F68.6 psig68.5 psig
R-407C at 40°F80.2 bubble / 63.2 dew psig81 / 64 psig

Differences of 1–2 psi from manufacturer charts are normal because of rounding and property models. Always follow the equipment manufacturer's charging data for field work.