Last reviewed: November 24, 2026
These pressure-temperature values are calculated reference data, not an official EPA or equipment-manufacturer table. CoolProp 8.1.0 uses Helmholtz-energy equations of state through its HEOS backend; blends use nominal ASHRAE 34 mass compositions.
Calculation method
- For R-410A, the blend is 50/50 R-32/R-125 by mass.
- For R-404A, the blend is 44/52/4 R-125/R-143a/R-134a by mass.
- For R-407C, the blend is 23/25/52 R-32/R-125/R-134a by mass.
- For R-454B, the blend is 68.9/31.1 R-32/R-1234yf by mass.
- Gauge pressure is calculated as psig = psia − 14.696 at sea level.
- Bubble pressure is saturated liquid; dew pressure is saturated vapor. The table spans −40°F to 150°F in 5°F steps.
Interpolated values and spot checks
Four values are log-interpolated where the solver did not return a point and are flagged in the CSV: R-410A at 110°F; R-407C at 135°F; and R-454B at 135°F and 145°F.
| Refrigerant and temperature | This chart | Published chart, approximately |
|---|---|---|
| R-410A at 75°F | 218.7 psig | 217 psig |
| R-22 at 40°F | 68.6 psig | 68.5 psig |
| R-407C at 40°F | 80.2 bubble / 63.2 dew psig | 81 / 64 psig |
Differences of 1–2 psi from manufacturer charts are normal because of rounding and property models. Always follow the equipment manufacturer's charging data for field work.