Values computed with CoolProp 8.1.0 (open-source thermophysical property library; Bell et al., Ind. Eng. Chem. Res. 2014) using Helmholtz-energy equations of state; blends modeled from their nominal ASHRAE 34 mass compositions. A few points near the top of the range were interpolated. For field work, confirm against the refrigerant manufacturer's PT chart.
R-407C saturation table
| Temp °F | Temp °C | Liquid / bubble (psig) | Vapor / dew (psig) |
|---|---|---|---|
| -40 °F | -40.0 °C | 2.7 psig | 4.7 in Hg vac |
| -35 °F | -37.2 °C | 5.1 psig | 0.8 in Hg vac |
| -30 °F | -34.4 °C | 7.7 psig | 1.6 psig |
| -25 °F | -31.7 °C | 10.6 psig | 3.9 psig |
| -20 °F | -28.9 °C | 13.7 psig | 6.5 psig |
| -15 °F | -26.1 °C | 17.2 psig | 9.3 psig |
| -10 °F | -23.3 °C | 20.9 psig | 12.3 psig |
| -5 °F | -20.6 °C | 25.0 psig | 15.7 psig |
| 0 °F | -17.8 °C | 29.5 psig | 19.4 psig |
| 5 °F | -15.0 °C | 34.3 psig | 23.5 psig |
| 10 °F | -12.2 °C | 39.5 psig | 27.9 psig |
| 15 °F | -9.4 °C | 45.2 psig | 32.7 psig |
| 20 °F | -6.7 °C | 51.2 psig | 37.9 psig |
| 25 °F | -3.9 °C | 57.7 psig | 43.5 psig |
| 30 °F | -1.1 °C | 64.7 psig | 49.6 psig |
| 35 °F | 1.7 °C | 72.2 psig | 56.1 psig |
| 40 °F | 4.4 °C | 80.2 psig | 63.2 psig |
| 45 °F | 7.2 °C | 88.8 psig | 70.7 psig |
| 50 °F | 10.0 °C | 97.9 psig | 78.8 psig |
| 55 °F | 12.8 °C | 107.6 psig | 87.5 psig |
| 60 °F | 15.6 °C | 117.9 psig | 96.8 psig |
| 65 °F | 18.3 °C | 128.9 psig | 106.7 psig |
| 70 °F | 21.1 °C | 140.5 psig | 117.3 psig |
| 75 °F | 23.9 °C | 152.8 psig | 128.5 psig |
| 80 °F | 26.7 °C | 165.8 psig | 140.5 psig |
| 85 °F | 29.4 °C | 179.6 psig | 153.2 psig |
| 90 °F | 32.2 °C | 194.1 psig | 166.7 psig |
| 95 °F | 35.0 °C | 209.4 psig | 181.0 psig |
| 100 °F | 37.8 °C | 225.5 psig | 196.1 psig |
| 105 °F | 40.6 °C | 242.4 psig | 212.1 psig |
| 110 °F | 43.3 °C | 260.3 psig | 229.0 psig |
| 115 °F | 46.1 °C | 279.0 psig | 246.9 psig |
| 120 °F | 48.9 °C | 298.6 psig | 265.8 psig |
| 125 °F | 51.7 °C | 319.2 psig | 285.7 psig |
| 130 °F | 54.4 °C | 340.7 psig | 306.6 psig |
| 135 °F | 57.2 °C | 363.3 psig | 328.8 psig |
| 140 °F | 60.0 °C | 386.9 psig | 352.1 psig |
| 145 °F | 62.8 °C | 411.7 psig | 376.6 psig |
| 150 °F | 65.6 °C | 437.5 psig | 402.5 psig |
R-407C chart FAQs
What is the pressure of R-407C at 75°F?
At 75°F, R-407C is approximately 152.8 psig liquid/bubble and 128.5 psig vapor/dew.
What is the boiling temperature of R-407C at 0 psig?
Zero gauge pressure is outside the published temperature range for R-407C.
Does R-407C have temperature glide?
Yes. At 75°F, the listed liquid/bubble and vapor/dew pressures differ by approximately 24.3 psi. Use bubble for liquid/subcooling and dew for vapor/superheat.
What is R-407C used for?
R-22 retrofits and some commercial AC. R-407C is a HFC blend with ASHRAE safety class A1 and a 100-year GWP of 1,774. SNAP-acceptable as an R-22 substitute in retrofit and new residential AC; above the 700 GWP limit for new systems installed from 2025.
Cite this chart: R-407C pressure-temperature chart, TradeCert Prep, computed with CoolProp 8.1.0, retrieved November 26, 2026. License CC BY 4.0.