Values computed with CoolProp 8.1.0 (open-source thermophysical property library; Bell et al., Ind. Eng. Chem. Res. 2014) using Helmholtz-energy equations of state; blends modeled from their nominal ASHRAE 34 mass compositions. A few points near the top of the range were interpolated. For field work, confirm against the refrigerant manufacturer's PT chart.
R-454B saturation table
| Temp °F | Temp °C | Liquid / bubble (psig) | Vapor / dew (psig) |
|---|---|---|---|
| -40 °F | -40.0 °C | 9.8 psig | 8.5 psig |
| -35 °F | -37.2 °C | 13.0 psig | 11.5 psig |
| -30 °F | -34.4 °C | 16.6 psig | 14.9 psig |
| -25 °F | -31.7 °C | 20.5 psig | 18.6 psig |
| -20 °F | -28.9 °C | 24.7 psig | 22.7 psig |
| -15 °F | -26.1 °C | 29.4 psig | 27.1 psig |
| -10 °F | -23.3 °C | 34.5 psig | 32.0 psig |
| -5 °F | -20.6 °C | 40.0 psig | 37.2 psig |
| 0 °F | -17.8 °C | 45.9 psig | 42.9 psig |
| 5 °F | -15.0 °C | 52.4 psig | 49.1 psig |
| 10 °F | -12.2 °C | 59.3 psig | 55.7 psig |
| 15 °F | -9.4 °C | 66.8 psig | 62.9 psig |
| 20 °F | -6.7 °C | 74.8 psig | 70.6 psig |
| 25 °F | -3.9 °C | 83.5 psig | 78.9 psig |
| 30 °F | -1.1 °C | 92.7 psig | 87.8 psig |
| 35 °F | 1.7 °C | 102.6 psig | 97.3 psig |
| 40 °F | 4.4 °C | 113.2 psig | 107.5 psig |
| 45 °F | 7.2 °C | 124.5 psig | 118.3 psig |
| 50 °F | 10.0 °C | 136.4 psig | 129.9 psig |
| 55 °F | 12.8 °C | 149.2 psig | 142.2 psig |
| 60 °F | 15.6 °C | 162.7 psig | 155.3 psig |
| 65 °F | 18.3 °C | 177.1 psig | 169.2 psig |
| 70 °F | 21.1 °C | 192.3 psig | 183.9 psig |
| 75 °F | 23.9 °C | 208.4 psig | 199.5 psig |
| 80 °F | 26.7 °C | 225.4 psig | 216.0 psig |
| 85 °F | 29.4 °C | 243.4 psig | 233.5 psig |
| 90 °F | 32.2 °C | 262.3 psig | 251.9 psig |
| 95 °F | 35.0 °C | 282.3 psig | 271.4 psig |
| 100 °F | 37.8 °C | 303.3 psig | 291.9 psig |
| 105 °F | 40.6 °C | 325.4 psig | 313.5 psig |
| 110 °F | 43.3 °C | 348.6 psig | 336.3 psig |
| 115 °F | 46.1 °C | 373.0 psig | 360.3 psig |
| 120 °F | 48.9 °C | 398.6 psig | 385.5 psig |
| 125 °F | 51.7 °C | 425.5 psig | 412.1 psig |
| 130 °F | 54.4 °C | 453.6 psig | 440.0 psig |
| 135 °F | 57.2 °C | 483.2 psig | 469.4 psig |
| 140 °F | 60.0 °C | 514.1 psig | 500.2 psig |
| 145 °F | 62.8 °C | 546.5 psig | 532.8 psig |
| 150 °F | 65.6 °C | 580.3 psig | 566.8 psig |
R-454B chart FAQs
What is the pressure of R-454B at 75°F?
At 75°F, R-454B is approximately 208.4 psig liquid/bubble and 199.5 psig vapor/dew.
What is the boiling temperature of R-454B at 0 psig?
Zero gauge pressure is outside the published temperature range for R-454B.
Does R-454B have temperature glide?
Yes. At 75°F, the listed liquid/bubble and vapor/dew pressures differ by approximately 8.9 psi. Use bubble for liquid/subcooling and dew for vapor/superheat.
What is R-454B used for?
New residential split AC and heat pumps (many manufacturers' R-410A successor). R-454B is a HFC/HFO blend with ASHRAE safety class A2L and a 100-year GWP of 465. SNAP-acceptable (with use conditions) for new residential and light-commercial AC; not listed for retrofits.
Cite this chart: R-454B pressure-temperature chart, TradeCert Prep, computed with CoolProp 8.1.0, retrieved November 26, 2026. License CC BY 4.0.