Values computed with CoolProp 8.1.0 (open-source thermophysical property library; Bell et al., Ind. Eng. Chem. Res. 2014) using Helmholtz-energy equations of state; blends modeled from their nominal ASHRAE 34 mass compositions. A few points near the top of the range were interpolated. For field work, confirm against the refrigerant manufacturer's PT chart.
R-1234yf saturation table
| Temp °F | Temp °C | Saturation (psig) |
|---|---|---|
| -40 °F | -40.0 °C | 11.6 in Hg vac |
| -35 °F | -37.2 °C | 9.0 in Hg vac |
| -30 °F | -34.4 °C | 6.1 in Hg vac |
| -25 °F | -31.7 °C | 2.9 in Hg vac |
| -20 °F | -28.9 °C | 0.4 psig |
| -15 °F | -26.1 °C | 2.3 psig |
| -10 °F | -23.3 °C | 4.4 psig |
| -5 °F | -20.6 °C | 6.7 psig |
| 0 °F | -17.8 °C | 9.2 psig |
| 5 °F | -15.0 °C | 11.9 psig |
| 10 °F | -12.2 °C | 14.9 psig |
| 15 °F | -9.4 °C | 18.1 psig |
| 20 °F | -6.7 °C | 21.6 psig |
| 25 °F | -3.9 °C | 25.4 psig |
| 30 °F | -1.1 °C | 29.4 psig |
| 35 °F | 1.7 °C | 33.8 psig |
| 40 °F | 4.4 °C | 38.4 psig |
| 45 °F | 7.2 °C | 43.4 psig |
| 50 °F | 10.0 °C | 48.8 psig |
| 55 °F | 12.8 °C | 54.5 psig |
| 60 °F | 15.6 °C | 60.6 psig |
| 65 °F | 18.3 °C | 67.1 psig |
| 70 °F | 21.1 °C | 74.0 psig |
| 75 °F | 23.9 °C | 81.3 psig |
| 80 °F | 26.7 °C | 89.0 psig |
| 85 °F | 29.4 °C | 97.3 psig |
| 90 °F | 32.2 °C | 106.0 psig |
| 95 °F | 35.0 °C | 115.2 psig |
| 100 °F | 37.8 °C | 124.9 psig |
| 105 °F | 40.6 °C | 135.1 psig |
| 110 °F | 43.3 °C | 145.9 psig |
| 115 °F | 46.1 °C | 157.3 psig |
| 120 °F | 48.9 °C | 169.2 psig |
| 125 °F | 51.7 °C | 181.8 psig |
| 130 °F | 54.4 °C | 195.0 psig |
| 135 °F | 57.2 °C | 208.9 psig |
| 140 °F | 60.0 °C | 223.4 psig |
| 145 °F | 62.8 °C | 238.7 psig |
| 150 °F | 65.6 °C | 254.7 psig |
R-1234yf chart FAQs
What is the pressure of R-1234yf at 75°F?
At 75°F, R-1234yf is approximately 81.3 psig.
What is the boiling temperature of R-1234yf at 0 psig?
At 0 psig, R-1234yf has a saturation temperature of approximately -21.1°F (and -29.5°C).
Does R-1234yf have temperature glide?
R-1234yf is single-component in this chart, so its bubble and dew pressures are the same at each listed temperature.
What is R-1234yf used for?
New vehicle AC; component of blends such as R-454B. R-1234yf is a HFO with ASHRAE safety class A2L and a 100-year GWP of 1. In use; vehicle AC service falls under Section 609, not 608.
Cite this chart: R-1234yf pressure-temperature chart, TradeCert Prep, computed with CoolProp 8.1.0, retrieved November 26, 2026. License CC BY 4.0.