Skip to content
TradeCert Prep
Pressure–temperature reference

R-1234yf Pressure Temperature Chart (°F and °C)

Quick answer: At 75°F, R-1234yf is about 81.3 psig. The full chart shows the database values every 5°F from -40°F to 150°F. Values are gauge pressure at sea level; use bubble for liquid-side subcooling and dew for vapor-side superheat. Confirm charging targets with the equipment manufacturer.

Last reviewed: November 24, 2026

Field lookup

Quick pressure and temperature lookup

The lookup linearly interpolates between the nearest published table points. Choose bubble for liquid/subcooling or dew for vapor/superheat.

Saturation—Single-component: one pressure for liquid and vapor

Jump to

Look up R-1234yf saturation pressure by temperature or estimate saturation temperature from pressure. Values are gauge pressure (psig) at sea level.

Values computed with CoolProp 8.1.0 (open-source thermophysical property library; Bell et al., Ind. Eng. Chem. Res. 2014) using Helmholtz-energy equations of state; blends modeled from their nominal ASHRAE 34 mass compositions. A few points near the top of the range were interpolated. For field work, confirm against the refrigerant manufacturer's PT chart.

Download CSV

R-1234yf saturation table

Saturation pressure values for R-1234yf. Negative gauge pressures are shown as inches of mercury vacuum.
Temp °FTemp °CSaturation (psig)
-40 °F-40.0 °C11.6 in Hg vac
-35 °F-37.2 °C9.0 in Hg vac
-30 °F-34.4 °C6.1 in Hg vac
-25 °F-31.7 °C2.9 in Hg vac
-20 °F-28.9 °C0.4 psig
-15 °F-26.1 °C2.3 psig
-10 °F-23.3 °C4.4 psig
-5 °F-20.6 °C6.7 psig
0 °F-17.8 °C9.2 psig
5 °F-15.0 °C11.9 psig
10 °F-12.2 °C14.9 psig
15 °F-9.4 °C18.1 psig
20 °F-6.7 °C21.6 psig
25 °F-3.9 °C25.4 psig
30 °F-1.1 °C29.4 psig
35 °F1.7 °C33.8 psig
40 °F4.4 °C38.4 psig
45 °F7.2 °C43.4 psig
50 °F10.0 °C48.8 psig
55 °F12.8 °C54.5 psig
60 °F15.6 °C60.6 psig
65 °F18.3 °C67.1 psig
70 °F21.1 °C74.0 psig
75 °F23.9 °C81.3 psig
80 °F26.7 °C89.0 psig
85 °F29.4 °C97.3 psig
90 °F32.2 °C106.0 psig
95 °F35.0 °C115.2 psig
100 °F37.8 °C124.9 psig
105 °F40.6 °C135.1 psig
110 °F43.3 °C145.9 psig
115 °F46.1 °C157.3 psig
120 °F48.9 °C169.2 psig
125 °F51.7 °C181.8 psig
130 °F54.4 °C195.0 psig
135 °F57.2 °C208.9 psig
140 °F60.0 °C223.4 psig
145 °F62.8 °C238.7 psig
150 °F65.6 °C254.7 psig

R-1234yf chart FAQs

What is the pressure of R-1234yf at 75°F?

At 75°F, R-1234yf is approximately 81.3 psig.

What is the boiling temperature of R-1234yf at 0 psig?

At 0 psig, R-1234yf has a saturation temperature of approximately -21.1°F (and -29.5°C).

Does R-1234yf have temperature glide?

R-1234yf is single-component in this chart, so its bubble and dew pressures are the same at each listed temperature.

What is R-1234yf used for?

New vehicle AC; component of blends such as R-454B. R-1234yf is a HFO with ASHRAE safety class A2L and a 100-year GWP of 1. In use; vehicle AC service falls under Section 609, not 608.

Cite this chart: R-1234yf pressure-temperature chart, TradeCert Prep, computed with CoolProp 8.1.0, retrieved November 26, 2026. License CC BY 4.0.

More about R-1234yf

R-1234yf is a HFO, ASHRAE safety class A2L, with a 100-year GWP of 1 and an ODP of 0. Typical use: new vehicle AC; component of blends such as R-454B. In use; vehicle AC service falls under Section 609, not 608.

Compare every refrigerant's class, safety and GWP in types of refrigerant, or see how the refrigeration cycle works.