Values computed with CoolProp 8.1.0 (open-source thermophysical property library; Bell et al., Ind. Eng. Chem. Res. 2014) using Helmholtz-energy equations of state; blends modeled from their nominal ASHRAE 34 mass compositions. A few points near the top of the range were interpolated. For field work, confirm against the refrigerant manufacturer's PT chart.
R-32 saturation table
| Temp °F | Temp °C | Saturation (psig) |
|---|---|---|
| -40 °F | -40.0 °C | 11.0 psig |
| -35 °F | -37.2 °C | 14.4 psig |
| -30 °F | -34.4 °C | 18.2 psig |
| -25 °F | -31.7 °C | 22.3 psig |
| -20 °F | -28.9 °C | 26.8 psig |
| -15 °F | -26.1 °C | 31.7 psig |
| -10 °F | -23.3 °C | 37.1 psig |
| -5 °F | -20.6 °C | 42.9 psig |
| 0 °F | -17.8 °C | 49.3 psig |
| 5 °F | -15.0 °C | 56.1 psig |
| 10 °F | -12.2 °C | 63.5 psig |
| 15 °F | -9.4 °C | 71.4 psig |
| 20 °F | -6.7 °C | 80.0 psig |
| 25 °F | -3.9 °C | 89.2 psig |
| 30 °F | -1.1 °C | 99.1 psig |
| 35 °F | 1.7 °C | 109.7 psig |
| 40 °F | 4.4 °C | 121.0 psig |
| 45 °F | 7.2 °C | 133.0 psig |
| 50 °F | 10.0 °C | 145.8 psig |
| 55 °F | 12.8 °C | 159.5 psig |
| 60 °F | 15.6 °C | 174.0 psig |
| 65 °F | 18.3 °C | 189.5 psig |
| 70 °F | 21.1 °C | 205.8 psig |
| 75 °F | 23.9 °C | 223.2 psig |
| 80 °F | 26.7 °C | 241.5 psig |
| 85 °F | 29.4 °C | 260.9 psig |
| 90 °F | 32.2 °C | 281.3 psig |
| 95 °F | 35.0 °C | 302.9 psig |
| 100 °F | 37.8 °C | 325.7 psig |
| 105 °F | 40.6 °C | 349.6 psig |
| 110 °F | 43.3 °C | 374.9 psig |
| 115 °F | 46.1 °C | 401.4 psig |
| 120 °F | 48.9 °C | 429.3 psig |
| 125 °F | 51.7 °C | 458.7 psig |
| 130 °F | 54.4 °C | 489.5 psig |
| 135 °F | 57.2 °C | 521.8 psig |
| 140 °F | 60.0 °C | 555.8 psig |
| 145 °F | 62.8 °C | 591.4 psig |
| 150 °F | 65.6 °C | 628.8 psig |
R-32 chart FAQs
What is the pressure of R-32 at 75°F?
At 75°F, R-32 is approximately 223.2 psig.
What is the boiling temperature of R-32 at 0 psig?
Zero gauge pressure is outside the published temperature range for R-32.
Does R-32 have temperature glide?
R-32 is single-component in this chart, so its bubble and dew pressures are the same at each listed temperature.
What is R-32 used for?
New residential split AC, heat pumps and mini-splits. R-32 is a HFC with ASHRAE safety class A2L and a 100-year GWP of 675. SNAP-acceptable (with use conditions) for new residential and light-commercial AC; not listed for retrofits.
Cite this chart: R-32 pressure-temperature chart, TradeCert Prep, computed with CoolProp 8.1.0, retrieved November 26, 2026. License CC BY 4.0.