Skip to content
TradeCert Prep
Pressure–temperature reference

R-12 Pressure Temperature Chart (°F and °C)

Quick answer: At 75°F, R-12 is about 76.8 psig. The full chart shows the database values every 5°F from -40°F to 150°F. Values are gauge pressure at sea level; use bubble for liquid-side subcooling and dew for vapor-side superheat. Confirm charging targets with the equipment manufacturer.

Last reviewed: November 24, 2026

Field lookup

Quick pressure and temperature lookup

The lookup linearly interpolates between the nearest published table points. Choose bubble for liquid/subcooling or dew for vapor/superheat.

Saturation—Single-component: one pressure for liquid and vapor

Jump to

Look up R-12 saturation pressure by temperature or estimate saturation temperature from pressure. Values are gauge pressure (psig) at sea level.

Values computed with CoolProp 8.1.0 (open-source thermophysical property library; Bell et al., Ind. Eng. Chem. Res. 2014) using Helmholtz-energy equations of state; blends modeled from their nominal ASHRAE 34 mass compositions. A few points near the top of the range were interpolated. For field work, confirm against the refrigerant manufacturer's PT chart.

Download CSV

R-12 saturation table

Saturation pressure values for R-12. Negative gauge pressures are shown as inches of mercury vacuum.
Temp °FTemp °CSaturation (psig)
-40 °F-40.0 °C11.0 in Hg vac
-35 °F-37.2 °C8.3 in Hg vac
-30 °F-34.4 °C5.5 in Hg vac
-25 °F-31.7 °C2.4 in Hg vac
-20 °F-28.9 °C0.5 psig
-15 °F-26.1 °C2.4 psig
-10 °F-23.3 °C4.5 psig
-5 °F-20.6 °C6.7 psig
0 °F-17.8 °C9.1 psig
5 °F-15.0 °C11.7 psig
10 °F-12.2 °C14.6 psig
15 °F-9.4 °C17.7 psig
20 °F-6.7 °C21.0 psig
25 °F-3.9 °C24.6 psig
30 °F-1.1 °C28.4 psig
35 °F1.7 °C32.5 psig
40 °F4.4 °C36.9 psig
45 °F7.2 °C41.6 psig
50 °F10.0 °C46.6 psig
55 °F12.8 °C51.9 psig
60 °F15.6 °C57.6 psig
65 °F18.3 °C63.7 psig
70 °F21.1 °C70.1 psig
75 °F23.9 °C76.8 psig
80 °F26.7 °C84.0 psig
85 °F29.4 °C91.6 psig
90 °F32.2 °C99.6 psig
95 °F35.0 °C108.0 psig
100 °F37.8 °C116.9 psig
105 °F40.6 °C126.3 psig
110 °F43.3 °C136.1 psig
115 °F46.1 °C146.4 psig
120 °F48.9 °C157.3 psig
125 °F51.7 °C168.6 psig
130 °F54.4 °C180.5 psig
135 °F57.2 °C193.0 psig
140 °F60.0 °C206.0 psig
145 °F62.8 °C219.7 psig
150 °F65.6 °C233.9 psig

R-12 chart FAQs

What is the pressure of R-12 at 75°F?

At 75°F, R-12 is approximately 76.8 psig.

What is the boiling temperature of R-12 at 0 psig?

At 0 psig, R-12 has a saturation temperature of approximately -21.5°F (and -29.7°C).

Does R-12 have temperature glide?

R-12 is single-component in this chart, so its bubble and dew pressures are the same at each listed temperature.

What is R-12 used for?

Pre-1990s refrigerators and vehicle AC. R-12 is a CFC with ASHRAE safety class A1 and a 100-year GWP of 10,900. CFC production was phased out in the U.S.; only recovered and reclaimed supply remains.

Cite this chart: R-12 pressure-temperature chart, TradeCert Prep, computed with CoolProp 8.1.0, retrieved November 26, 2026. License CC BY 4.0.

More about R-12

R-12 is a CFC, ASHRAE safety class A1, with a 100-year GWP of 10,900 and an ODP of 1. Typical use: pre-1990s refrigerators and vehicle AC. CFC production was phased out in the U.S.; only recovered and reclaimed supply remains.

Compare every refrigerant's class, safety and GWP in types of refrigerant, or see how the refrigeration cycle works.