Values computed with CoolProp 8.1.0 (open-source thermophysical property library; Bell et al., Ind. Eng. Chem. Res. 2014) using Helmholtz-energy equations of state; blends modeled from their nominal ASHRAE 34 mass compositions. A few points near the top of the range were interpolated. For field work, confirm against the refrigerant manufacturer's PT chart.
R-12 saturation table
| Temp °F | Temp °C | Saturation (psig) |
|---|---|---|
| -40 °F | -40.0 °C | 11.0 in Hg vac |
| -35 °F | -37.2 °C | 8.3 in Hg vac |
| -30 °F | -34.4 °C | 5.5 in Hg vac |
| -25 °F | -31.7 °C | 2.4 in Hg vac |
| -20 °F | -28.9 °C | 0.5 psig |
| -15 °F | -26.1 °C | 2.4 psig |
| -10 °F | -23.3 °C | 4.5 psig |
| -5 °F | -20.6 °C | 6.7 psig |
| 0 °F | -17.8 °C | 9.1 psig |
| 5 °F | -15.0 °C | 11.7 psig |
| 10 °F | -12.2 °C | 14.6 psig |
| 15 °F | -9.4 °C | 17.7 psig |
| 20 °F | -6.7 °C | 21.0 psig |
| 25 °F | -3.9 °C | 24.6 psig |
| 30 °F | -1.1 °C | 28.4 psig |
| 35 °F | 1.7 °C | 32.5 psig |
| 40 °F | 4.4 °C | 36.9 psig |
| 45 °F | 7.2 °C | 41.6 psig |
| 50 °F | 10.0 °C | 46.6 psig |
| 55 °F | 12.8 °C | 51.9 psig |
| 60 °F | 15.6 °C | 57.6 psig |
| 65 °F | 18.3 °C | 63.7 psig |
| 70 °F | 21.1 °C | 70.1 psig |
| 75 °F | 23.9 °C | 76.8 psig |
| 80 °F | 26.7 °C | 84.0 psig |
| 85 °F | 29.4 °C | 91.6 psig |
| 90 °F | 32.2 °C | 99.6 psig |
| 95 °F | 35.0 °C | 108.0 psig |
| 100 °F | 37.8 °C | 116.9 psig |
| 105 °F | 40.6 °C | 126.3 psig |
| 110 °F | 43.3 °C | 136.1 psig |
| 115 °F | 46.1 °C | 146.4 psig |
| 120 °F | 48.9 °C | 157.3 psig |
| 125 °F | 51.7 °C | 168.6 psig |
| 130 °F | 54.4 °C | 180.5 psig |
| 135 °F | 57.2 °C | 193.0 psig |
| 140 °F | 60.0 °C | 206.0 psig |
| 145 °F | 62.8 °C | 219.7 psig |
| 150 °F | 65.6 °C | 233.9 psig |
R-12 chart FAQs
What is the pressure of R-12 at 75°F?
At 75°F, R-12 is approximately 76.8 psig.
What is the boiling temperature of R-12 at 0 psig?
At 0 psig, R-12 has a saturation temperature of approximately -21.5°F (and -29.7°C).
Does R-12 have temperature glide?
R-12 is single-component in this chart, so its bubble and dew pressures are the same at each listed temperature.
What is R-12 used for?
Pre-1990s refrigerators and vehicle AC. R-12 is a CFC with ASHRAE safety class A1 and a 100-year GWP of 10,900. CFC production was phased out in the U.S.; only recovered and reclaimed supply remains.
Cite this chart: R-12 pressure-temperature chart, TradeCert Prep, computed with CoolProp 8.1.0, retrieved November 26, 2026. License CC BY 4.0.