Skip to content
TradeCert Prep
Pressure–temperature reference

R-123 Pressure Temperature Chart (°F and °C)

Quick answer: At 75°F, R-123 is about 4.1 in Hg vac. The full chart shows the database values every 5°F from -40°F to 150°F. Values are gauge pressure at sea level; use bubble for liquid-side subcooling and dew for vapor-side superheat. Confirm charging targets with the equipment manufacturer.

Last reviewed: November 24, 2026

Field lookup

Quick pressure and temperature lookup

The lookup linearly interpolates between the nearest published table points. Choose bubble for liquid/subcooling or dew for vapor/superheat.

Saturation—Single-component: one pressure for liquid and vapor

Jump to

Look up R-123 saturation pressure by temperature or estimate saturation temperature from pressure. Values are gauge pressure (psig) at sea level.

Values computed with CoolProp 8.1.0 (open-source thermophysical property library; Bell et al., Ind. Eng. Chem. Res. 2014) using Helmholtz-energy equations of state; blends modeled from their nominal ASHRAE 34 mass compositions. A few points near the top of the range were interpolated. For field work, confirm against the refrigerant manufacturer's PT chart.

Download CSV

R-123 saturation table

Saturation pressure values for R-123. Negative gauge pressures are shown as inches of mercury vacuum.
Temp °FTemp °CSaturation (psig)
-40 °F-40.0 °C28.9 in Hg vac
-35 °F-37.2 °C28.7 in Hg vac
-30 °F-34.4 °C28.5 in Hg vac
-25 °F-31.7 °C28.1 in Hg vac
-20 °F-28.9 °C27.7 in Hg vac
-15 °F-26.1 °C27.5 in Hg vac
-10 °F-23.3 °C27.1 in Hg vac
-5 °F-20.6 °C26.5 in Hg vac
0 °F-17.8 °C25.9 in Hg vac
5 °F-15.0 °C25.2 in Hg vac
10 °F-12.2 °C24.6 in Hg vac
15 °F-9.4 °C23.8 in Hg vac
20 °F-6.7 °C22.8 in Hg vac
25 °F-3.9 °C21.8 in Hg vac
30 °F-1.1 °C20.8 in Hg vac
35 °F1.7 °C19.5 in Hg vac
40 °F4.4 °C18.1 in Hg vac
45 °F7.2 °C16.7 in Hg vac
50 °F10.0 °C15.1 in Hg vac
55 °F12.8 °C13.2 in Hg vac
60 °F15.6 °C11.2 in Hg vac
65 °F18.3 °C9.0 in Hg vac
70 °F21.1 °C6.7 in Hg vac
75 °F23.9 °C4.1 in Hg vac
80 °F26.7 °C1.2 in Hg vac
85 °F29.4 °C0.9 psig
90 °F32.2 °C2.5 psig
95 °F35.0 °C4.2 psig
100 °F37.8 °C6.1 psig
105 °F40.6 °C8.1 psig
110 °F43.3 °C10.3 psig
115 °F46.1 °C12.6 psig
120 °F48.9 °C15.1 psig
125 °F51.7 °C17.7 psig
130 °F54.4 °C20.6 psig
135 °F57.2 °C23.6 psig
140 °F60.0 °C26.8 psig
145 °F62.8 °C30.2 psig
150 °F65.6 °C33.8 psig

R-123 chart FAQs

What is the pressure of R-123 at 75°F?

At 75°F, R-123 is approximately 4.1 in Hg vac.

What is the boiling temperature of R-123 at 0 psig?

At 0 psig, R-123 has a saturation temperature of approximately 82.0°F (and 27.8°C).

Does R-123 have temperature glide?

R-123 is single-component in this chart, so its bubble and dew pressures are the same at each listed temperature.

What is R-123 used for?

Low-pressure centrifugal chillers. R-123 is a HCFC with ASHRAE safety class B1 and a 100-year GWP of 77. All HCFC production and import ends in 2030.

Cite this chart: R-123 pressure-temperature chart, TradeCert Prep, computed with CoolProp 8.1.0, retrieved November 26, 2026. License CC BY 4.0.

More about R-123

R-123 is a HCFC, ASHRAE safety class B1, with a 100-year GWP of 77 and an ODP of 0.02. Typical use: low-pressure centrifugal chillers. All HCFC production and import ends in 2030.

Compare every refrigerant's class, safety and GWP in types of refrigerant, or see how the refrigeration cycle works.