Skip to content
TradeCert Prep
Pressure–temperature reference

R-134a Pressure Temperature Chart (°F and °C)

Quick answer: At 75°F, R-134a is about 78.7 psig. The full chart shows the database values every 5°F from -40°F to 150°F. Values are gauge pressure at sea level; use bubble for liquid-side subcooling and dew for vapor-side superheat. Confirm charging targets with the equipment manufacturer.

Last reviewed: November 24, 2026

Field lookup

Quick pressure and temperature lookup

The lookup linearly interpolates between the nearest published table points. Choose bubble for liquid/subcooling or dew for vapor/superheat.

Saturation—Single-component: one pressure for liquid and vapor

Jump to

Look up R-134a saturation pressure by temperature or estimate saturation temperature from pressure. Values are gauge pressure (psig) at sea level.

Values computed with CoolProp 8.1.0 (open-source thermophysical property library; Bell et al., Ind. Eng. Chem. Res. 2014) using Helmholtz-energy equations of state; blends modeled from their nominal ASHRAE 34 mass compositions. A few points near the top of the range were interpolated. For field work, confirm against the refrigerant manufacturer's PT chart.

Download CSV

R-134a saturation table

Saturation pressure values for R-134a. Negative gauge pressures are shown as inches of mercury vacuum.
Temp °FTemp °CSaturation (psig)
-40 °F-40.0 °C14.9 in Hg vac
-35 °F-37.2 °C12.4 in Hg vac
-30 °F-34.4 °C9.8 in Hg vac
-25 °F-31.7 °C6.9 in Hg vac
-20 °F-28.9 °C3.7 in Hg vac
-15 °F-26.1 °C0.0 psig
-10 °F-23.3 °C1.9 psig
-5 °F-20.6 °C4.1 psig
0 °F-17.8 °C6.5 psig
5 °F-15.0 °C9.1 psig
10 °F-12.2 °C11.9 psig
15 °F-9.4 °C15.0 psig
20 °F-6.7 °C18.4 psig
25 °F-3.9 °C22.1 psig
30 °F-1.1 °C26.1 psig
35 °F1.7 °C30.4 psig
40 °F4.4 °C35.0 psig
45 °F7.2 °C40.1 psig
50 °F10.0 °C45.4 psig
55 °F12.8 °C51.2 psig
60 °F15.6 °C57.4 psig
65 °F18.3 °C64.0 psig
70 °F21.1 °C71.1 psig
75 °F23.9 °C78.7 psig
80 °F26.7 °C86.7 psig
85 °F29.4 °C95.2 psig
90 °F32.2 °C104.3 psig
95 °F35.0 °C113.9 psig
100 °F37.8 °C124.2 psig
105 °F40.6 °C135.0 psig
110 °F43.3 °C146.4 psig
115 °F46.1 °C158.4 psig
120 °F48.9 °C171.2 psig
125 °F51.7 °C184.6 psig
130 °F54.4 °C198.7 psig
135 °F57.2 °C213.6 psig
140 °F60.0 °C229.2 psig
145 °F62.8 °C245.7 psig
150 °F65.6 °C262.9 psig

R-134a chart FAQs

What is the pressure of R-134a at 75°F?

At 75°F, R-134a is approximately 78.7 psig.

What is the boiling temperature of R-134a at 0 psig?

At 0 psig, R-134a has a saturation temperature of approximately -15.0°F (and -26.1°C).

Does R-134a have temperature glide?

R-134a is single-component in this chart, so its bubble and dew pressures are the same at each listed temperature.

What is R-134a used for?

Medium-temperature refrigeration, centrifugal chillers, older vehicle AC. R-134a is a HFC with ASHRAE safety class A1 and a 100-year GWP of 1,430. In use; new equipment in many sectors is moving to lower-GWP refrigerants under the HFC phasedown.

Cite this chart: R-134a pressure-temperature chart, TradeCert Prep, computed with CoolProp 8.1.0, retrieved November 26, 2026. License CC BY 4.0.

More about R-134a

R-134a is a HFC, ASHRAE safety class A1, with a 100-year GWP of 1,430 and an ODP of 0. Typical use: medium-temperature refrigeration, centrifugal chillers, older vehicle AC. In use; new equipment in many sectors is moving to lower-GWP refrigerants under the HFC phasedown.