Values computed with CoolProp 8.1.0 (open-source thermophysical property library; Bell et al., Ind. Eng. Chem. Res. 2014) using Helmholtz-energy equations of state; blends modeled from their nominal ASHRAE 34 mass compositions. A few points near the top of the range were interpolated. For field work, confirm against the refrigerant manufacturer's PT chart.
R-134a saturation table
| Temp °F | Temp °C | Saturation (psig) |
|---|---|---|
| -40 °F | -40.0 °C | 14.9 in Hg vac |
| -35 °F | -37.2 °C | 12.4 in Hg vac |
| -30 °F | -34.4 °C | 9.8 in Hg vac |
| -25 °F | -31.7 °C | 6.9 in Hg vac |
| -20 °F | -28.9 °C | 3.7 in Hg vac |
| -15 °F | -26.1 °C | 0.0 psig |
| -10 °F | -23.3 °C | 1.9 psig |
| -5 °F | -20.6 °C | 4.1 psig |
| 0 °F | -17.8 °C | 6.5 psig |
| 5 °F | -15.0 °C | 9.1 psig |
| 10 °F | -12.2 °C | 11.9 psig |
| 15 °F | -9.4 °C | 15.0 psig |
| 20 °F | -6.7 °C | 18.4 psig |
| 25 °F | -3.9 °C | 22.1 psig |
| 30 °F | -1.1 °C | 26.1 psig |
| 35 °F | 1.7 °C | 30.4 psig |
| 40 °F | 4.4 °C | 35.0 psig |
| 45 °F | 7.2 °C | 40.1 psig |
| 50 °F | 10.0 °C | 45.4 psig |
| 55 °F | 12.8 °C | 51.2 psig |
| 60 °F | 15.6 °C | 57.4 psig |
| 65 °F | 18.3 °C | 64.0 psig |
| 70 °F | 21.1 °C | 71.1 psig |
| 75 °F | 23.9 °C | 78.7 psig |
| 80 °F | 26.7 °C | 86.7 psig |
| 85 °F | 29.4 °C | 95.2 psig |
| 90 °F | 32.2 °C | 104.3 psig |
| 95 °F | 35.0 °C | 113.9 psig |
| 100 °F | 37.8 °C | 124.2 psig |
| 105 °F | 40.6 °C | 135.0 psig |
| 110 °F | 43.3 °C | 146.4 psig |
| 115 °F | 46.1 °C | 158.4 psig |
| 120 °F | 48.9 °C | 171.2 psig |
| 125 °F | 51.7 °C | 184.6 psig |
| 130 °F | 54.4 °C | 198.7 psig |
| 135 °F | 57.2 °C | 213.6 psig |
| 140 °F | 60.0 °C | 229.2 psig |
| 145 °F | 62.8 °C | 245.7 psig |
| 150 °F | 65.6 °C | 262.9 psig |
R-134a chart FAQs
What is the pressure of R-134a at 75°F?
At 75°F, R-134a is approximately 78.7 psig.
What is the boiling temperature of R-134a at 0 psig?
At 0 psig, R-134a has a saturation temperature of approximately -15.0°F (and -26.1°C).
Does R-134a have temperature glide?
R-134a is single-component in this chart, so its bubble and dew pressures are the same at each listed temperature.
What is R-134a used for?
Medium-temperature refrigeration, centrifugal chillers, older vehicle AC. R-134a is a HFC with ASHRAE safety class A1 and a 100-year GWP of 1,430. In use; new equipment in many sectors is moving to lower-GWP refrigerants under the HFC phasedown.
Cite this chart: R-134a pressure-temperature chart, TradeCert Prep, computed with CoolProp 8.1.0, retrieved November 26, 2026. License CC BY 4.0.