Skip to content
TradeCert Prep
Pressure–temperature reference

R-404A Pressure Temperature Chart (°F and °C)

Quick answer: At 75°F, R-404A is about 162.0 psig liquid/bubble and 160.1 psig vapor/dew. The full chart shows the database values every 5°F from -40°F to 150°F. Values are gauge pressure at sea level; use bubble for liquid-side subcooling and dew for vapor-side superheat. Confirm charging targets with the equipment manufacturer.

Last reviewed: November 24, 2026

Field lookup

Quick pressure and temperature lookup

The lookup linearly interpolates between the nearest published table points. Choose bubble for liquid/subcooling or dew for vapor/superheat.

Liquid (bubble)—Use for subcooling (liquid line)
Vapor (dew)—Use for superheat (suction line)

Jump to

Look up R-404A saturation pressure by temperature or estimate saturation temperature from pressure. Values are gauge pressure (psig) at sea level.

Values computed with CoolProp 8.1.0 (open-source thermophysical property library; Bell et al., Ind. Eng. Chem. Res. 2014) using Helmholtz-energy equations of state; blends modeled from their nominal ASHRAE 34 mass compositions. A few points near the top of the range were interpolated. For field work, confirm against the refrigerant manufacturer's PT chart.

Download CSV

R-404A saturation table

Saturation pressure values for R-404A. Negative gauge pressures are shown as inches of mercury vacuum.
Temp °FTemp °CLiquid / bubble (psig)Vapor / dew (psig)
-40 °F-40.0 °C4.9 psig4.3 psig
-35 °F-37.2 °C7.5 psig6.8 psig
-30 °F-34.4 °C10.3 psig9.6 psig
-25 °F-31.7 °C13.4 psig12.7 psig
-20 °F-28.9 °C16.8 psig16.0 psig
-15 °F-26.1 °C20.5 psig19.7 psig
-10 °F-23.3 °C24.6 psig23.6 psig
-5 °F-20.6 °C28.9 psig27.9 psig
0 °F-17.8 °C33.7 psig32.6 psig
5 °F-15.0 °C38.8 psig37.7 psig
10 °F-12.2 °C44.3 psig43.1 psig
15 °F-9.4 °C50.2 psig49.0 psig
20 °F-6.7 °C56.6 psig55.3 psig
25 °F-3.9 °C63.4 psig62.1 psig
30 °F-1.1 °C70.7 psig69.3 psig
35 °F1.7 °C78.6 psig77.1 psig
40 °F4.4 °C86.9 psig85.4 psig
45 °F7.2 °C95.8 psig94.2 psig
50 °F10.0 °C105.3 psig103.6 psig
55 °F12.8 °C115.3 psig113.6 psig
60 °F15.6 °C126.0 psig124.2 psig
65 °F18.3 °C137.3 psig135.5 psig
70 °F21.1 °C149.3 psig147.4 psig
75 °F23.9 °C162.0 psig160.1 psig
80 °F26.7 °C175.4 psig173.4 psig
85 °F29.4 °C189.5 psig187.5 psig
90 °F32.2 °C204.5 psig202.4 psig
95 °F35.0 °C220.2 psig218.1 psig
100 °F37.8 °C236.8 psig234.6 psig
105 °F40.6 °C254.2 psig252.0 psig
110 °F43.3 °C272.5 psig270.4 psig
115 °F46.1 °C291.8 psig289.6 psig
120 °F48.9 °C312.0 psig309.9 psig
125 °F51.7 °C333.3 psig331.2 psig
130 °F54.4 °C355.6 psig353.5 psig
135 °F57.2 °C379.1 psig377.0 psig
140 °F60.0 °C403.7 psig401.7 psig
145 °F62.8 °C429.6 psig427.7 psig
150 °F65.6 °C456.8 psig455.1 psig

R-404A chart FAQs

What is the pressure of R-404A at 75°F?

At 75°F, R-404A is approximately 162.0 psig liquid/bubble and 160.1 psig vapor/dew.

What is the boiling temperature of R-404A at 0 psig?

Zero gauge pressure is outside the published temperature range for R-404A.

Does R-404A have temperature glide?

Yes. At 75°F, the listed liquid/bubble and vapor/dew pressures differ by approximately 1.9 psi. Use bubble for liquid/subcooling and dew for vapor/superheat.

What is R-404A used for?

Low- and medium-temperature commercial refrigeration. R-404A is a HFC blend with ASHRAE safety class A1 and a 100-year GWP of 3,922. In use for existing equipment; new commercial refrigeration is shifting to lower-GWP refrigerants.

Cite this chart: R-404A pressure-temperature chart, TradeCert Prep, computed with CoolProp 8.1.0, retrieved November 26, 2026. License CC BY 4.0.

More about R-404A

R-404A is a HFC blend (R-125/R-143a/R-134a, 44/52/4 by mass), ASHRAE safety class A1, with a 100-year GWP of 3,922 and an ODP of 0. Typical use: low- and medium-temperature commercial refrigeration. In use for existing equipment; new commercial refrigeration is shifting to lower-GWP refrigerants.

Compare every refrigerant's class, safety and GWP in types of refrigerant, or see how the refrigeration cycle works.